1.4.5
Run and stop (STF, STR, STOP)
(common
)
To start and stop the motor, first switch ON the input power
of the inverter (turn ON the MC at the operation-ready
when there is an MC on the input side). Then start the
motor with the forward or reverse rotation start signal.
(1) Two-wire type (STF, STR)
A two-wire type connection is shown below.
1) Forward/reverse rotation signal is used as both
the start and stop signals. Turn ON either of the
forward and reverse rotation signals to start the
motor in the corresponding direction. Switching
ON or OFF both the start signals during operation
will decelerate the inverter to a stop.
2) The speed setting signals may either be given by
entering 0 to 5VDC across the frequency setting
input terminal 2-5, by setting three speed [
Pr. 4 to
Pr. 6
] (high, middle, low speeds), etc.
(For multi-speed operation, refer to page 48.)
3) After the start signal has been input, the inverter
starts operating when the frequency setting signal
reaches or exceeds the [
Pr. 13 Starting frequency
].
If the motor load torque is large or the [
Pr. 0 Torque
boost
] setting is small, operation may not be
started due to insufficient torque until the inverter
output frequency reaches about 3 to 6Hz.
If the [
Pr. 2 Minimum frequency
] is set to 6Hz, for
example, merely entering the start signal causes
the running frequency to reach the minimum
frequency of 6Hz according to the [
Pr. 7
Acceleration time
].
4) To stop the motor, operate the DC injection brake
for the period of time set in [
Pr. 11 DC injection
brake operation time
] at not more than the DC
injection brake operation frequency or at not more
than 0.5Hz.
To disable the DC injection brake function, set 0 in
either of [
Pr. 11 DC injection brake operation time
] or
[
Pr. 12 DC injection brake voltage
].
In this case, the motor is coasted to a stop at not
more than the frequency set in [
Pr. 10 DC injection
brake operation frequency
] or at not more than
0.5Hz (when the DC injection brake is not
operated).
5) If the reverse rotation signal is input during
forward rotation or the forward rotation signal is
input during reverse rotation, output
characteristics change without going through the
stop mode.
(2) Three-wire type connection (STF, STR,
STOP)
A three-wire type connection is shown below.
1) Turn ON the STOP signal to enable the start self-
holding function. In this case, the forward/reverse
rotation signal functions only as a start signal.
2) If the start signals STF (STR) are turned ON once,
then OFF, the start signals are kept ON and starts
the inverter. When changing the direction of
rotation, turn STR (STF) signal ON once and then
OFF.
3) The inverter is decelerated to a stop by turning
OFF the STOP signal once. For the frequency
setting signal and the operation of DC injection
brake at a stop time, refer to paragraphs 2) to 4) in
(1) Two-wire type connection.
4) When the signal JOG is turned ON, terminal
STOP signal is invalid and JOG operation has
precedence.
5) If MRS signal is turned ON, the self-holding
function is not deactivated.
(3) Start signal selection
common
common
STF
STR
[
Pr. 250
] Setting Inverter State
0 to 100s, 9999
1000 to 1100s,
8888
OFF
OFF
Stop
Stop
OFF
ON
Reverse rotation
ON
OFF
Forward rotation
Forward rotation
ON
ON
Stop
Reverse rotation
common
Two wire-type connection
([
Pr. 250 = 9999
])
Two wire-type connection
([
Pr. 250 = 8888
])
Three wire-type connection
Example
[
Pr. 250 = 9999
]
Three wire-type connection
Example
([
Pr. 250 = 8888
])
Forward
rotation start
Reverse
rotation start
STF
ON
Time
STF
STR Inverter
Output frequency
ON
STR
10
2
5
Forward
rotation
Reverse
rotation
SD
Start signal
Forward/
reverse
signal
STF
Time
STF
STR Inverter
Output frequency
STR
10
2
5
Forward
rotation
Reverse
rotation
ON
ON
SD
Stop
Forward
rotation start
Reverse
rotation start
STF
STR
STOP
Inverter
Time
STF
STR
ON
STOP
OFF
Output frequency
ON
Forward
rotation
Reverse
rotation
OFF
ON
SD
ON
Time
Stop
Forward rotation
/reverse rotation
Start
STF
STR
ON
STOP ON
STF
STR
STOP
Inverter
Output frequency
ON
OFF
OFF
Forward
rotation
Reverse
rotation
SD
ON