SPECIFICATIONS
1.4.20 Output current detection function (Y12, Y13)
(common)
[Pr. ]
Name
Initial Value
Setting
Range
Description
Available
Inverters
150
Output current detection
level
150%
120%
0 to 220%
0 to 150%
0 to 200%
Set the output current detection level.
100% is the rated inverter current.
○
○
151
Output current detection
signal delay time
0s
0 to 10s
Set the output current detection
period. Set the time from when the
output current has risen above the
setting until the output current
detection signal (Y12) is output.
○
○
152
Zero current detection
level
5%
0 to 220%
0 to 150%
0 to 200%
Set the zero current detection level.
Suppose that the rated inverter current
is 100%.
○
○
153
Zero current detection
period
0.5s
0 to 1s
Set this parameter to define the period
from when the output current drops
below the [
Pr. 152
] setting until the zero
current detection signal (Y13) is
output.
○
○
166
Output current detection
signal retention time
0.1s
0 to 10s
Set the retention time when the Y12
signal is ON.
○
―
9999
The Y12 signal ON status is retained.
The signal is turned OFF at the next
start.
167
Output current detection
operation selection
0
0
Operation continues when the Y12
signal is ON.
○
―
1
The inverter is brought to trip (E.CDO)
when the Y12 signal is ON.
common
A700
F700
D700
E700
E700 D700
A700
F700
A700
F700
E700 D700
A700
F700
E700 D700