Output side earth
(ground) fault
overcurrent
The inverter trips if an earth (ground) fault
overcurrent flows due to an earth (ground)
fault that occurred on the inverter's output
side (load side).
(E.GF)
Ground Fault
{
{
—
—
Output side earth
(ground) fault
overcurrent at start
The inverter trips if [
Pr. 249 Earth (ground)
fault detection at start
] is set active (=1) and
an earth (ground) fault overcurrent flows at
start due to an earth (ground) fault that
occurred on the inverter's output side (load
side).
(E.GF)
Ground Fault
—
—
{
{
External thermal
relay operation
If the external thermal relay provided for
motor overheat protection or the internally
mounted temperature relay in the motor, etc.
switches ON (contacts open), the inverter
output is stopped.
(E.OHT)
OH Fault
{
{
{
{
PTC thermistor
operation
For
, the fault appears when the
motor overheat status is detected for 10s or
more by the external PTC thermistor input
connected to the terminal AU.
For
, inverter trips when resistance of
PTC thermistor connected between terminal
2 and terminal 10 is more than the value set
in [
Pr.561 PTC thermistor protection level
].
(E.PTC)
Fault 14
PTC
activated
{
{
—
{
Option fault
Appears when the AC power supply is
connected to the terminal R/L1, S/L2, T/L3
accidentally when a high power factor
converter is connected.
Appears when the switch for the
manufacturer setting of the plug-in option is
changed.
For
, it appears when torque
command by the plug-in option is selected
using [
Pr. 804 Torque command source
selection
] and no plug-in option is mounted.
(E.OPT)
Option Fault
{
{
—
—
Communication
option fault
Stops the inverter output when a
communication line fault occurs in the
communication option.
(E.OP1)
Option1 Fault
—
{
{
—
(E.OP3)
Option3 Fault
{
—
—
—
Option fault
Stops the inverter output if a contact fault or
the like of the connector between the
inverter and built-in option occurs or if a
communication option is fitted to the
connector 1 or 2 (
only).
Appears when the switch for the
manufacturer setting of the plug-in option is
changed.
(E.1)
Fault 1
{
{
{
—
(E.2)
Fault 2
{
—
—
—
(E.3)
Fault 3
{
—
—
—
Param
e
ter
st
orage devic
e
faul
t
Control
circuit board
Appears when a fault occurred in
parameters stored (EEPROM failure)
(E.PE)
Corrupt Memry
{
{
{
{
Main circuit
board
(E.PE2)
Fault 14
PR
storage
alarm
{
{
—
—
Internal board fault
When a combination of control board and
main circuit board is wrong, the inverter is
tripped.
(E.PE2)
Fault 14
PR
storage
alarm
—
—
{
—
Name
Description
Indication
Available Inverters
Operation
panel
Parameter unit
FR-PU04 FR-PU07
A700
F700
E700
D700
A700 F700
D700
A700
A700