546
SELECTION
(1) Inverter-generated heat
When the rated output current flows, the inverter
generates heat as shown on the preceding page.
1) Reduction according to motor load factor
At the rated output current, the following figure
shows a reduction rate when operating the
inverter with a light load.
2) Reduction according to duty
The ratio of reduction during intermittent operation
in a cycle of within five minutes is shown.
Electricity during standby (at a stop)
200V class
Inverter Capacity (kW)
Standby Electricity (W)
Fan is ON
Fan is OFF
0.4
0.75
9 (without fan)
0.75
1.5
9 (without fan)
1.5
2.2
13
11
2.2
3.7
13
11
3.7
5.5
13
11
5.5
7.5
19
11
7.5
11
19
11
11
15
22
14
15
18.5
25
15
18.5
22
25
15
22
30
27
15
400V class
Inverter Capacity (kW)
Standby Electricity (W)
Fan is ON
Fan is OFF
0.4
0.75
14 (without fan)
0.75
1.5
14 (without fan)
1.5
2.2
14 (without fan)
2.2
3.7
16
14
3.7
5.5
16
14
5.5
7.5
23
15
7.5
11
23
15
11
15
26
18
15
18.5
26
18
18.5
22
28
18
22
30
28
18
100
90
80
70
60
Heat generated(%)
Motor load factor(%)
0
20
40
60
80
100
Indicates motor capacity
0.75kW or less
1.5 to
7.5 kW
11kW or mo
re
Load factor versus heat generated
(when motor and inverter have the same rank)
100
75
50
25
0
20
100
40
60
80
Duty (%ED)
Heat generated(%)
Duty versus heat generated
A700
F700
A700
F700