230
PARAMETER
(1) Selection of digital input [
Pr. 304
]
16bit (12bit) digital input is available when [
Pr. 304
9999
].
Use [
Pr. 304
] to select BCD code input ([
Pr. 304
] = 0,
2, 10, 12) or binary input ([
Pr. 304
= 1, 3, 11, 13]). For
BCD code, input data is read as decimal. For binary
input, input data is read as hexadecimal.
When 3 digits BCD code input or 12bit binary input is
selected, X12 to X15 signal of plug-in option FR-
A7AX is invalid.
When [
Pr. 304 = 2, 3, 12, 13
], output frequency is a
sum of digital input command and terminal 1
compensation input.
When switching the inputs e.g. between volume input
to perform manual operation and BCD code input to
perform automatic operation, set the BCD code input
to "0" under manual operation.
The priorities of the frequency setting are as follows.
"JOG
Multi-speed operation (RH, RM, RL)
PID (X14)
AU (terminal 4)
Digital command by
the FR-A7AX
terminal 2" (When digital input is
valid, terminal 2 is invalid.)
[Example] To input BCD code 6325
[Example] To input binary AB65
H
(2) Data read timing [
Pr. 305
]
When [
Pr. 305 = 0, 10
], the set frequency data entered
from the digital signal input terminals (X0 to X15) is
always imported independently of whether the DY
signal of plug-in option FR-A7AX is ON or OFF.
When [
Pr. 305 = 10
], filter is active for reading, and
compensation for a digital signal change timing of
each bit is available.
When [
Pr. 305 = 1
], the set frequency data entered
from the digital signal input terminals (X0 to X15) is
imported only when the DY signal is ON. The set
frequency data is not imported when the DY signal is
OFF. Therefore, even if the input status of the X0-X15
signal changes, the set frequency data before OFF of
the DY signal is valid.
Each terminal from X0 to X15 is all recognized as
OFF when the inverter is turned ON in terminal DY
OFF status.
BCD Code Input
Digit
Terminal
name
Terminal input
state
Input
value
1
X0
ON
5
X1
OFF
X2
ON
X3
OFF
10
X4
OFF
2
X5
ON
X6
OFF
X7
OFF
100
X8
ON
3
X9
ON
X10
OFF
X11
OFF
1000
X12
OFF
6
X13
ON
X14
ON
X15
OFF
* When the signal is used to enter a BCD code, 0A
H
to
0F
H
entries are ignored during operation and the
previous inputs are used to continue operation. 0A
H
to 0F
H
input are ignored.
If binary input is changed to BCD code input with
0A
H
to 0F
H
input, the set frequency becomes 0Hz.
Binary Input
Terminal
name
Terminal input
state
Input
value
(hexade-
cimal)
Input
value
(decimal)
X0
ON
5
43877
X1
OFF
X2
ON
X3
OFF
X4
OFF
6
X5
ON
X6
ON
X7
OFF
X8
ON
B
X9
ON
X10
OFF
X11
ON
X12
OFF
A
X13
ON
X14
OFF
X15
ON
Filter [
Pr. 305
= "10"]
20ms maximum
Digital signal input
(terminal X0 to X15)
Set frequency
Reflected on
the set frequency
20ms or more necessary*
* Hold the digital signal input (X0 to X15) status for 20ms or more.
Changing the signal within 20ms may not reflect it on the set
frequency.
Digital signal input
(terminal X0 to X15)
1ms or more
1ms or more
Data read timing signal
(terminal DY)
OFF
ON
ON
20ms or more
necessary