329
PARAMETER
2
P
ARAM
ETE
R
(3) Operation voltage (torque) setting [Pr. 12]
Use [
Pr. 12
] to set the percentage to the power supply
voltage. (For
, this parameter is not used
during zero speed control or servo lock.)
When [
Pr. 12
= 0%], the DC injection brake is
disabled. (At a stop, the motor coasts.)
Even [
Pr. 12
] setting is set larger, braking torque is
limited so that output current is within the inverter
rated current.
When using the constant-torque motor (SF-JRCA)
and energy saving motor (SF-HR, SF-HRCA),
change the [
Pr. 12
] setting as follows:
For the 5.5K, 7.5K, when the [
Pr. 12
] setting is the
following, changing the [
Pr. 71 Applied motor
] setting
automatically changes the [
Pr. 12
] setting. Therefore,
it is not necessary to change the [
Pr. 12
] setting.
SF-JRCA: 3.7K or less ...4%, 5.5K to 55K ...2%
SF-HR, SF-HRCA: 3.7K or less...4%, 5.5K, 7.5K...3%,
11K to 55K...2% (30K...1.5%)
A700
[Pr. 71] Setting
Standard
Motor
(Initial Value)
Constant-
torque
Motor
0.1K, 0.2K
6%
4%
0.4K to 3.7K
4%
4%
5.5K, 7.5K
4%
2%
11K to 55K
2%
2%
75K or more
1%
1%