511
SELECTION
S
E
LECTION
3
(d) Calculation of outgoing harmonic current of
each degree
Note that the harmonic content is as
indicated in the table on the next page.
(If the consumer has a facility to reduce
harmonic currents, its effect may be taken
into consideration.)
Outgoing harmonic current
= Rated current converted from received power
voltage
maximum operation ratio
harmonic content
10
3
[mA]
Fundamental wave currents and rated capacities of
inverters
Motor
Capacity
[kW]
Fundamental Wave
Current [A]
Rated Capacity
[kVA]
200V
400V
200V
400V
0.4
1.61
0.81
0.57
0.75
2.74
1.37
0.97
1.5
5.50
2.75
1.95
2.2
7.93
3.96
2.81
3.7
13.0
6.5
4.61
5.5
19.1
9.55
6.77
7.5
25.6
12.8
9.07
11
36.9
18.5
13.1
15
49.8
24.9
17.6
18.5
61.4
30.7
21.8
22
73.1
36.6
25.9
30
98.0
49.0
34.7
37
121
60.4
42.8
45
147
73.5
52.1
55
180
89.9
63.7
75
245
123
87.2
90
293
147
104
110
357
179
127
132
—
216
153
160
—
258
183
220
—
355
252
250
—
403
286
280
—
450
319
315
—
506
359
355
—
571
405
400
—
643
456
450
—
723
512
500
—
804
570
560
—
900
638