PARAMETER
2
P
ARAM
ETE
R
E700
D700
Signal
Terminal Used
Function
Description
Parameter Setting
Input
X14
Depending on
[
Pr. 178 to
184
]
[
Pr. 178 to
182
]
PID control
selection
Turn ON X14 signal to perform PID
control.
Set 14 in any of
[
Pr. 178
to
184
]
[
Pr. 178
to
182
]
2
2
Set point input
You can input the set point for PID
control.
[
Pr. 128
= 20, 21 ]
[
Pr. 133
= 9999 ]
0 to 5V .............0 to 100%
Pr. 73
= 1
, 11 ]
0 to 10V ...........0 to 100%
[
Pr. 73
= 0, 10 ]
PU
—
Set point input
Set the set point [
Pr. 133
] from the
operation panel.
[
Pr. 128
= 20, 21 ]
[
Pr. 133
= 0 to 100% ]
4
4
Measured value
input
Input the signal from the detector
(measured value signal).
[
Pr. 128
= 20, 21 ]
4 to 20mA ........0 to 100%
[
Pr. 267
= 0
]
0 to 5V .............0 to 100%
[
Pr. 267
= 1 ]
0 to 10V ...........0 to 100%
[
Pr. 267
= 2 ]
Ou
tp
u
t
FUP
Depending on
[
Pr. 190 to
Pr. 192
]
[
Pr. 190,
Pr. 192
]
Upper limit output
Output to indicate that the process value
signal exceeded the maximum value
[
Pr.
131
].
[
Pr. 128
= 20, 21 ]
[
Pr. 131
≠
9999 ]
Set 15 or 115
[
Pr. 190 to Pr. 192
]
[
Pr. 190
or
Pr. 192
]
FDN
Lower limit output
Output when the process value signal
falls below the minimum value [
Pr. 132
].
[
Pr. 128
= 20, 21 ]
[
Pr. 132
≠
9999 ]
Set 14 or 114
[
Pr. 190 to Pr. 192
]
[
Pr. 190
or
Pr. 192
]
RL
Forward (reverse)
rotation direction
output
"Hi" is output to indicate that the output
indication of the parameter unit is
forward rotation (FWD) or "Low" to
indicate that it is reverse rotation (REV)
or stop (STOP).
Set 16 or 116
[
Pr. 190 to Pr. 192
]
[
Pr. 190
or
Pr. 192
]
PID
During PID control
activated
Turns ON during PID control.
Set 47 or 147
in
[
Pr. 190 to Pr. 192
]
[
Pr. 190
or
Pr. 192
]
SLEEP
(Only in
)
PID output
interruption
Turns ON when the PID output
interruption function is performed.
Pr. 575
≠
9999 ]
Set 70 or 170
Pr. 190
or
Pr.192
]
SE
SE
Output terminal
common
Common terminal for open collector
output terminal.
*1
When the X14 signal is not assigned, only the [
Pr. 128
≠
0] setting makes PID control valid.
*2
The shaded area indicates the parameter initial value.
*3
When 100 or larger value is set in any of
Pr.190 to Pr.192 (output terminal function selection)
, the terminal output has negative
logic.
(Refer to page 61 for details)
*4
When [
Pr. 561 PTC thermistor protection level
≠
"9999"], terminal 2 is not available for set point input.
Use
[
Pr. 133
]
for set point
input. (Only in
)
*5
Refer to the LONWORKS communication option (FR-A7NL E kit) instruction manual for the setting method from LONWORKS
communication.
Refer to the CC-Link communication option (FR-A7NC E kit) instruction manual for the setting method from CC-Link
communication. (Only in
)
E700
D700
E700
D700
E700
D700
E700
D700
E700
D700
E700
D700
E700
D700
D700
D700
E700
Summary of Contents for FR-A700 Series
Page 245: ...279 2 PARAMETER PARAMETER MEMO ...
Page 440: ...474 PARAMETER MEMO ...
Page 522: ...556 SELECTION MEMO ...