SPECIFICATIONS
*1
The applied motor capacity indicated is the maximum capacity applicable for use of the Mitsubishi 4-pole standard motor.
*2
The rated output capacity indicated assumes that the output voltage is 220V for 200V class and 440V for 400V class.
*3
When operating the inverter of 75K or more with a value larger than 2kHz set in [
Pr. 72 PWM frequency selection
], the rated output
current is the value in parenthesis.
*4
The % value of the overload current rating indicated is the ratio of the overload current to the inverter's rated output current. For
repeated duty, allow time for the inverter and motor to return to or below the temperatures under 100% load.
*5
The maximum output voltage does not exceed the power supply voltage. The maximum output voltage can be changed within
the setting range. However, the pulse voltage value of the inverter output side voltage remains unchanged at about that of
the power supply.
*6
200V: When FR-ABR (option) is connected, 150% torque 10% ED for 0.4K and 0.75K, 100% torque 10%ED for 1.5K to 7.5K,
100% torque 6%ED for 11K to 22K.
400V: When FR-ABR-H (option) is connected, 15% torque 10% ED for 0.4K to 7.5K, 100% torque 6% ED for 11K to 22K.
*7
The power supply capacity varies with the value of the power supply side inverter impedance (including those of the input
reactor and cables).
*8
When the hook of the inverter front cover is cut off for installation of the plug-in option, protective structure of the inverter
changes to an open type (IP00).
*9
FR-DU07 : IP40 (except for the PU connector)
Type FR-A740-
K
75
90
110
132
160
185
220
250
280
315
355
400
450
500
Applicable motor capacity
(kW)
*1
75
90
110
132
160
185
220
250
280
315
355
400
450
500
Ou
tp
u
t
Rated capacity (kVA)
*2
110
137
165
198
248
275
329
367
417
465
521
587
660
733
Rated current (A)
*3
144
(122)
180
(153)
216
(184)
260
(221)
325
(276)
361
(307)
432
(367)
481
(409)
547
(465)
610
(519)
683
(581)
770
(655)
866
(736)
962
(818)
Overload current rating
*4
150% 60s, 200% 3s (inverse-time characteristics) surrounding air temperature 50
Voltage
*5
Three-phase 380 to 480V
Regenerative
braking torque
Maximum value/
permissible duty
10% torque/continuous
Power supply
Rated input AC voltage/
frequency
Three-phase 380 to 480V 50Hz/60Hz
Permissible AC voltage
fluctuation
323 to 528V 50Hz/60Hz
Permissible frequency
fluctuation
±5%
Power supply
system
capacity
(kVA)
*7
Without DC
reactor
—
—
—
—
—
—
—
—
—
—
—
—
—
—
With DC
reactor
110
137
165
198
248
275
329
367
417
465
521
587
660
733
Protective structure (JEM
1030)
*9
Open type (IP00)
Cooling system
Forced air cooling
Approximate mass (kg)
50
57
72
72
110
110
175
175
175
260
260
370
370
370