447
PARAMETER
2
P
ARAM
ETE
R
(4) Data definitions
1) Control codes
2) Inverter station number
Specify the station number of the inverter which
communicates with the computer.
3) Instruction code
Specify the processing request, e.g. operation or
monitoring, given by the computer to the inverter.
Hence, the inverter can be run and monitored in
various ways by specifying the instruction code as
appropriate. (Refer to page 452)
4) Data
Indicates the data such as frequency and
parameters transferred to and from the inverter.
The definitions and ranges of set data are
determined in accordance with the instruction
codes. (Refer to page 452)
5) Waiting time
Specify the waiting time between the receipt of
data at the inverter from the computer and the
transmission of reply data. Set the waiting time in
accordance with the response time of the
computer between 0 and 150ms in 10ms
increments. (e.g. 1 = 10ms, 2 = 20ms).
When the [
Pr. 123, Pr. 337 Waiting time setting
9999
], create the communication request data
without waiting time in the data format. (The
number of characters decreases by 1.)
The data check time changes depending on the
instruction code. (Refer to page 448)
6) Sum check code
The sum check code is 2-digit ASCII
(hexadecimal) representing the lower 1 byte (8
bits) of the sum (binary) derived from the checked
ASCII data.
[Example 1] Computer inverter
* When the [
Pr. 123, 337 Waiting time setting
9999
], create the
communication request data without waiting time in the data
format.
[Example 2] Computer inverter
Signal
Name
ASCII
Code
Description
STX
H02
Start of Text (start of data)
ETX
H03
End of Text (end of data)
ENQ
H05
Enquiry (communication request)
ACK
H06
Acknowledge (no data error detected)
LF
H0A
Line Feed
CR
H0D
Carriage Return
NAK
H15
Negative Acknowledge (data error
detected)
Computer
Inverter
Inverter
Computer
Inverter data processing time
=
+
Waiting time
(setting 10ms)
data check time
(About 10 to 30ms,
which depends on the
instruction code)
ENQ
*W
aiting
time
1
Instruction
code
Station
number
0
1
Data
E
1
0
7
A
D
F
4
H05
H30 H31
H31
H45 H31
H30 H37 H41 H44 H46 H34
Binary code
H30
H30
H31 H45 H31 H31
H37
H41
H44
= H1F4
Sum
ASCII Code
+
+
+
+
+
+
+
+
Sum
check
code
STX
Data read
Station
number
0
1
1
7
0
3
0
H02
H30 H31
H37
H31 H37
H30 H03 H33 H30
Sum
ETX
7
ASCII Code
Binary code
= H130
Sum
check
code
H31
H30 H31
H37
H37
H30
+
+
+
+
+