2.21 Communication operation
2.21.1 Operation mode selection [Pr. 79, 340]
(common)
When power is switched on or when power comes back on after instantaneous power failure, the inverter can be started up in
the Network operation mode. After the inverter has started up in the Network operation mode, parameter write and operation
can be performed from a program. Set this mode for communication operation using the inverter RS-485 terminals or
communication option.
The above parameters can be changed during a stop in any operation mode.
*1
However, the parameters can be set whenever the communication option is connected. Changed setting value is valid when
powering on or resetting the inverter.
(1) Operation mode at power-on [
Pr. 340
]
*1
Setting values 2 and 12 for [Pr.340] are available only for
. These setting values are mainly used in a communication
operation with RS-485 terminal. When [
Pr. 57 Restart coasting time 9999
] (automatic restart after instantaneous power failure is
selected) , the inverter will resume the same operation state which was in before after power has been restored from an
instantaneous power failure.
*2
The operation mode cannot be switched directly between the PU operation mode and Network operation mode.
*3
Operation mode can be changed between the PU operation mode and Network operation mode with
key of the control
panel (PU07) and X65 signal.
common
[Pr. ]
Name
Initial
Value
Setting
Range
Description
Available
Inverters
79
Operation mode
selection
0
0 to 4, 6,
7
Select the operation mode.
(Refer to page 209)
{
{
340
*1
Communication
startup mode
selection
0
0
As set in [
Pr. 79
].
{
{
1
Started in network operation mode.
When the setting is 2, it will resume the pre-instantaneous power failure
operation mode after an instantaneous power failure occurs.
{
{
2
{
—
10
Started in network operation mode. Operation mode can be changed between
the PU operation mode and Network operation mode from the operation panel.
When the setting is 12, it will resume the pre-instantaneous power failure
operation mode after an instantaneous power failure occurs.
{
{
12
{
—
A700
F700
E700
D700
Depending on the [
Pr. 79
] and [
Pr. 340
] settings, the operation mode at power-ON (reset) changes as described below.
[Pr. 340]
Setting
[Pr. 79]
Setting
Operation Mode at Power ON
or Power Restoration or Reset
Operation Mode Switching
0
(initial
value)
0
(initial
value)
External operation mode
Switching among the External, PU, and NET operation mode is enabled
*2
1
PU operation mode
PU operation mode fixed
2
External operation mode
Switching between the External and NET operation mode is enabled
Switching to PU operation mode is disabled
3, 4
External/PU combined operation mode
Operation mode switching is disabled
6
External operation mode
Switching among the External, PU, and NET operation mode is enabled while
running
7
X12 (MRS) signal ON
External
operation mode
Switching among the External, PU, and NET operation mode is enabled
*2
X12 (MRS) signal OFF
External
operation mode
Fixed to External operation mode (forcibly switched to external operation mode)
1, 2
*1
0
NET operation mode
Same as when [
Pr. 340 = 0
]
1
PU operation mode
2
NET operation mode
3, 4
External/PU combined operation mode
6
NET operation mode
7
X12 (MRS) signal ON
NET
operation mode
X12 (MRS) signal OFF
External
operation mode
10, 12
*1
0
NET operation mode
Switching between the PU and NET operation mode is enabled
*3
1
PU operation mode
Same as when [
Pr. 340 = 0
]
2
NET operation mode
Fixed to NET operation mode
3, 4
External/PU combined operation mode
Same as when [
Pr. 340 = 0
]
6
NET operation mode
Switching between the PU and NET operation mode is enabled while running
*3
7
External operation mode
Same as when [
Pr. 340 = 0
]