![Mitsubishi Electric FR-A700 Series Technical Manual Download Page 143](http://html.mh-extra.com/html/mitsubishi-electric/fr-a700-series/fr-a700-series_technical-manual_239199143.webp)
152
152
PARAMETER
PARAMETER
PA
R
A
M
E
T
E
R
2
2.1.2
FR-F700
In the initial setting, only the simple mode parameters are displayed. Set [
Pr. 160 User group read selection
] as required.
• indicates simple mode parameters.
• The parameters marked with
in the table allow its setting to be changed during operation even if 0 (initial value) is
set in [
Pr. 77 Parameter write selection
] .
• Symbols in the option column indicate parameters which function when an option is mounted.
......... FR-A7AX, .......... FR-A7AY, .......... FR-A7AR,
......... FR-A7NC, ......... FR-A7ND, ......... FR-A7NL,
......... FR-A7NP
• These instruction codes are used for parameter read and write by using Mitsubishi inverter protocol with the RS-485
communication.
• Symbols in the control mode-based correspondence table indicate the following;
{
: Usable parameter
×
: Unusable parameter
• Symbols in the parameter copy, parameter clear, and all parameter clear columns indicate the following;
{
: Valid
×
: Invalid
[Pr. ]
Name
Initial
Value
Setting
Range
Remarks
160
User group read selection
9999
9999
Only the simple mode parameters can be displayed.
0
Simple mode+extended mode parameters can be displayed.
1
Only the parameters registered to the user group can be
displayed.
[Pr.]
Name
Setting Range
Minimum Setting
Increments
Initial value Reference
[Pr.]
Option
Instruction Code
Control Mode-based
Correspondence Table
Parameter
Copy
Parameter
Clear
All Parameter
Clear
Read
Write Extended
V/F
control
Simple
magnetic
flux vector
control
Bas
ic
f
unct
ions
0
Torque boost
0 to 30%
0.1%
6/4/3/2/
0
00
80
0
{
×
{
{
{
1
Maximum frequency
0 to 120Hz
0.01Hz
120/60Hz
1
01
81
0
{
{
{
{
{
2
Minimum frequency
0 to 120Hz
0.01Hz
0Hz
2
02
82
0
{
{
{
{
{
3
Base frequency
0 to 400Hz
0.01Hz
60Hz
3
03
83
0
{
{
{
{
{
4
Multi-speed setting (high speed)
0 to 400Hz
0.01Hz
60Hz
4
04
84
0
{
{
{
{
{
5
Multi-speed setting (middle speed)
0 to 400Hz
0.01Hz
30Hz
5
05
85
0
{
{
{
{
{
6
Multi-speed setting (low speed)
0 to 400Hz
0.01Hz
10Hz
6
06
86
0
{
{
{
{
{
7
Acceleration time
0 to 3600/360s
0.1/0.01s
5/15s
7
07
87
0
{
{
{
{
{
8
Deceleration time
0 to 3600/360s
0.1/0.01s
10/30s
8
08
88
0
{
{
{
{
{
9
Electronic thermal O/L relay
0 to 500/0 to 3600A
0.01/0.1A
Rated inverter
current
9
09
89
0
{
{
{
{
{
DC i
n
jec
tion
brak
e
10
DC injection brake operation frequency
0 to 120Hz, 9999
0.01Hz
3Hz
10
0A
8A
0
{
{
{
{
{
11
DC injection brake operation time
0 to 10s
0.1s
0.5s
11
0B
8B
0
{
{
{
{
{
12
DC injection brake operation voltage
0 to 30%
0.1%
4/2/1%
12
0C
8C
0
{
{
{
{
{
—
13
Starting frequency
0 to 60Hz
0.01Hz
0.5Hz
13
0D
8D
0
{
{
{
{
{
—
14
Load pattern selection
0, 1
1
1
14
0E
8E
0
{
{
{
{
{
Jog
operat
ion
15
Jog frequency
0 to 400Hz
0.01Hz
5Hz
15
0F
8F
0
{
{
{
{
{
16
Jog acceleration/deceleration time
0 to 3600/360s
0.1/0.01s
0.5s
16
10
90
0
{
{
{
{
{
—
17
MRS input selection
0, 2
1
0
17
11
91
0
{
{
{
{
{
—
18
High speed maximum frequency
120 to 400Hz
0.01Hz
120/60Hz
18
12
92
0
{
{
{
{
{
—
19
Base frequency voltage
0 to 1000V, 8888, 9999
0.1V
9999
19
13
93
0
{
{
{
{
{
A
ccel
e
rat
ion/
dec
el
er
at
ion t
ime
20
Acceleration/deceleration reference
frequency
1 to 400Hz
0.01Hz
60Hz
20
14
94
0
{
{
{
{
{
21
Acceleration/deceleration time increments 0, 1
1
0
21
15
95
0
{
{
{
{
{
St
al
l
pr
ev
en
tio
n
22
Stall prevention operation level
0 to 150%, 9999
0.1%
120%
22
16
96
0
{
{
{
{
{
23
Stall prevention operation level
compensation factor at double speed
0 to 200%, 9999
0.1%
9999
23
17
97
0
{
{
{
{
{
M
u
lti-s
peed
se
tt
in
g
24
Multi-speed setting (speed 4)
0 to 400Hz, 9999
0.01Hz
9999
24
18
98
0
{
{
{
{
{
25
Multi-speed setting (speed 5)
0 to 400Hz, 9999
0.01Hz
9999
25
19
99
0
{
{
{
{
{
26
Multi-speed setting (speed 6)
0 to 400Hz, 9999
0.01Hz
9999
26
1A
9A
0
{
{
{
{
{
27
Multi-speed setting (speed 7)
0 to 400Hz, 9999
0.01Hz
9999
27
1B
9B
0
{
{
{
{
{
Summary of Contents for FR-A700 Series
Page 245: ...279 2 PARAMETER PARAMETER MEMO ...
Page 440: ...474 PARAMETER MEMO ...
Page 522: ...556 SELECTION MEMO ...