6
SPECIFICATIONS
(3) FR-E700
z
Three-phase 200V power supply
z
Three-phase 400V power supply
*1
The applicable motor capacity indicated is the maximum capacity applicable for use of the Mitsubishi 4-pole standard motor.
*2
The rated output capacity indicated assumes that the output voltage is 230V for three-phase 200V class and 440V for three-
phase 400V class.
*3
The % value of the overload current rating indicated is the ratio of the overload current to the inverter's rated output current. For
repeated duty, allow time for the inverter and motor to return to or below the temperatures under 100% load.
*4
The maximum output voltage does not exceed the power supply voltage. The maximum output voltage can be changed within
the setting range. However, the pulse voltage value of the inverter output side voltage remains unchanged at about
that of
the power supply.
*5
The power supply capacity varies with the value of the power supply side inverter impedance (including those of the input
reactor and cables).
*6
Setting 2kHz or more in
Pr. 72 PWM frequency selection
to perform low acoustic noise operation in the surrounding air
temperature exceeding 40°C (totally-enclosed structure is 30°C), the rated output current is the value in parenthesis.
*7
y
Connect DC power supply to terminal P/+ and N/-. Connect the plus side of the power supply to terminal P/+ and minus side to
terminal N/-.
y
Since the voltage between P/+ and N/- may increase due to the regeneration energy from the motor and exceeds 415V tempo-
rarily, select the DC power supply which can withstand the voltage/energy during regeneration. If using the power supply which
can not withstand voltage/energy during regeneration, insert diodes in series for reverse current prevention.
y
Although the FR-E700 series has the built-in inrush current limit circuit, select the DC power supply considering the inrush cur-
rent at powering ON as the inrush current four times of the rated inverter flows at powering ON.
y
Since the power supply capacity depends on the output impedance of the power, select the power supply capacity which has
enough allowance according to the AC power supply system capacity.
*8
Totally enclosed structure series ends with -C.
Type FR-E720-
K(-C)
∗8
0.1
0.2
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
15
Applicable motor capacity (kW)
0.1
0.2
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
15
Ou
tp
u
t
Rated capacity (kVA)
0.3
0.6
1.2
2.0
3.2
4.4
7.0
9.5
13.1
18.7
23.9
Rated current (A)
0.8
(0.8)
1.5
(1.4)
3
(2.5)
5
(4.1)
8
(7)
11
(10)
17.5
(16.5)
24
(23)
33
(31)
47
(44)
60
(57)
Overload current rating
150% 60s, 200% 3s (inverse-time characteristics)
Voltage
∗4
Three-phase 200 to 240V
P
o
wer supply
Rated input
AC (DC) voltage/frequency
Three-phase 200 to 240V 50Hz/60Hz (283 to 339VDC
∗7
)
Permissible AC (DC) voltage
fluctuation
170 to 264V 50Hz/60Hz (240 to 373VDC
Permissible frequency fluctuation
±5%
Power supply capacity (kVA)
0.4
0.8
1.5
2.5
4.5
5.5
9
12
17
20
28
Protective structure (JEM1030)
Enclosed type (IP20). IP40 for totally enclosed structure series.
Cooling system
Self-cooling
Forced air cooling
Approximate mass (kg)
0.5
0.5
0.7
1.0
1.4
1.4
1.7
4.3
4.3
9.0
9.0
Type FR-E740-
K(-C)
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
15
Applicable motor capacity (kW)
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
15
Ou
tp
u
t
Rated capacity (kVA)
1.2
2.0
3.0
4.6
7.2
9.1
13.0
17.5
23.0
Rated current (A)
1.6
(1.4)
2.6
(2.2)
4.0
(3.8)
6.0
(5.4)
9.5
(8.7)
12
17
23
30
Overload current rating
150% 60s, 200% 3s (inverse-time characteristics)
Voltage
Three-phase 380 to 480V
Power
s
uppl
y
Rated input voltage/frequency
Three-phase 380 to 480V 50Hz/60Hz
Permissible AC voltage fluctuation
325 to 528V 50Hz/60Hz
Permissible frequency fluctuation
±5%
Power supply capacity (kVA)
1.5
2.5
4.5
5.5
9.5
12
17
20
28
Protective structure (JEM1030)
Enclosed type (IP20). IP40 for totally enclosed structure series.
Cooling system
Self-cooling
Forced air cooling
Approximate mass (kg)
1.4
1.4
1.9
1.9
1.9
3.2
3.2
5.9
5.9
2