320
PARAMETER
2.12 Adjustment of Real sensorless vector control,
vector control
2.12.1 Bias and gain of torque (magnetic flux) setting voltage (current)
[Pr. 241, C16 to C19 (Pr. 919, 920), C34 to C37 (Pr. 928, 929), C38 to C41 (Pr. 932,
933)]
(A700)
You can set the magnitude (slope) of the torque as desired
in relation to the torque setting signal (0 to 5VDC, 0 to 10V
or 4 to 20mA).
Set [
Pr. 73, Pr. 267
] to switch between 0 to 5VDC, 0 to
10VDC and 4 to 20mA. (Refer to page 217)
In the initial setting status, terminal 1 and terminal 4 used
for analog input are respectively set to speed setting
auxiliary (speed limit auxiliary) and speed command
(speed limit). To use an analog input terminal as torque
command, torque limit, and magnetic flux input, set [
Pr. 868
Terminal 1 function assignment
] and [
Pr. 858 Terminal 4
function assignment
] to change functions. (Refer to page 46)
Magnetic flux is valid only during vector control.
To use terminal 6 of FR-A7AZ for torque command or
torque limit, set [
Pr. 406 High resolution analog input selection
]
and change the function. (Refer to page 46)
A700
[Pr. ]
Name
Initial
Value
Setting
Range
Description
241
*1
Analog input display unit switchover
0
0
Displayed in %
Selects the unit for analog input display.
1
Displayed in V/mA
C16(919)
Terminal 1 bias command (torque/
magnetic flux)
0%
0 to 400%
Set the torque (magnetic flux) on the bias side of terminal 1
input.
C17(919) Terminal 1 bias (torque/magnetic flux)
0%
0 to 300%
Set the converted % of the bias side voltage of terminal 1
input.
C18(920)
Terminal 1 gain command (torque/
magnetic flux))
150%
0 to 400%
Set the torque (magnetic flux) of the terminal 1 input gain
(maximum).
C19(920) Terminal 1 gain (torque/magnetic flux)
100%
0 to 300%
Set the converted % of the gain side voltage of terminal 1
input.
C34(928) Terminal 6 bias command (torque)
0%
0 to 400% Set the torque on the bias side of terminal 6 input.
C35(928) Terminal 6 bias (torque)
0%
0 to 300%
Set the converted % of the bias side voltage of terminal 6
input.
C36(929) Terminal 6 gain command (torque)
150%
0 to 400% Set the torque of the terminal 6 input gain (maximum).
C37(929) Terminal 6 gain (torque)
100%
0 to 300%
Set the converted % of the gain side voltage of terminal 6
input.
C38(932)
Terminal 4 bias command (torque/
magnetic flux)
0%
0 to 400%
Set the torque (magnetic flux) on the bias side of terminal 4
input.
C39(932) Terminal 4 bias (torque/magnetic flux)
20%
0 to 300%
Set the converted % of the bias side current (voltage) of
terminal 4 input.
C40(933)
Terminal 4 gain command (torque/
magnetic flux)
150%
0 to 400%
Set the torque (magnetic flux) of the terminal 4 input gain
(maximum).
C41(933) Terminal 4 gain (torque/magnetic flux)
100%
0 to 300%
Set the converted % of the gain side current (voltage) of
terminal 4 input.
*1
The above parameters allow its setting to be changed during operation in any operation mode even if "0" (initial value) is set in
[
Pr. 77 Parameter write selection
].