260
PARAMETER
(5) Performing Advanced magnetic vector
control by switching between two motors
Turning the RT signal ON allows the second motor to
be controlled.
Set the second motor in [
Pr. 450 Second applied motor
].
(Initial setting is 9999 (without second applied motor).
Refer to page 266.)
1)
2)
Turning the RT signal ON allows the second motor to
be controlled. Set the second motor in [
Pr. 450 Second
applied motor
].
Note that control method is not selectable for the
second motor, so the same control method as the
first motor applies. When Advanced magnetic vector
control is selected, use same type of motor for the
first and second motors. Use X18 signal when you
want to use the second motor in V/F control.
Functions
RT Signal is ON
(Second Motor)
RT Signal is OFF
(First Motor)
Applied motor
[
Pr. 450
]
[
Pr. 71
]
Motor capacity
[
Pr. 453
]
[
Pr. 80
]
Number of motor
poles
[
Pr. 454
]
[
Pr. 81
]
Speed control gain
[
Pr. 569
]
[
Pr. 89
]
Control method
selection
[
Pr. 451
]
[
Pr. 800
]
A700
E700