Hot-swap
power supply 2
Power supply
filler panel
Figure 216. Power supply removal
Step 5.
If you are instructed to return the power supply, follow all packaging instructions, and use any
packaging materials for shipping that are supplied to you.
Replacing a hot-swap dc power supply
Use this information to replace a hot-swap dc power supply.
The following notes describe the type of power supply that the server supports and other information that
you must consider when you install a power supply:
• Before you install an additional power supply or replace a power supply with one of a different wattage,
you may use the Power Configurator utility to determine current system power consumption. For more
information and to download the utility, go to http://www.ibm.com/systems/bladecenter/resources/
powerconfig.html.
• Before you install an additional power supply or replace a power supply with one of a different wattage,
go to Table 2 “Power supply configurations” on page 9 for detailed configurations.
• The server comes with one hot-swap 12-volt output power supply that connects to power supply bay 1.
The input voltage is -48 V dc or -60 V dc auto-sensing.
• Before you install a dc power supply in the server, you must remove all ac power supplies. Do not use
both ac and dc power supplies in the same server. Install up to two dc power supplies or up to two ac
power supplies, but not a combination.
• Power supply 1 is the default/primary power supply. If power supply 1 fails, you must replace the power
supply with the same wattage immediately.
• You can order an optional power supply for redundancy.
• These power supplies are designed for parallel operation. In the event of a power-supply failure, the
redundant power supply continues to power the system. The server supports a maximum of two
power supplies.
• It is the customer's responsibility to supply the necessary power cable.
To reduce the risk of electric shock or energy hazards:
–
Use a circuit breaker that is rated at 25 amps.
–
Use 2.5 mm
2
(12 AWG) at 90° C copper wire.
–
Torque the wiring-terminal screws to 0.50 ~ 0.60 newton-meters (4.43 ~ 5.31 inch-pounds).
306
Lenovo System x3650 M4 Installation and Service Guide
Summary of Contents for x3650 M4 BD 5466
Page 1: ...Lenovo System x3650 M4 Installation and Service Guide Machine Type 7915 ...
Page 6: ...iv Lenovo System x3650 M4 Installation and Service Guide ...
Page 176: ...164 Lenovo System x3650 M4 Installation and Service Guide ...
Page 226: ...214 Lenovo System x3650 M4 Installation and Service Guide ...
Page 1042: ...1030 Lenovo System x3650 M4 Installation and Service Guide ...
Page 1200: ...1188 Lenovo System x3650 M4 Installation and Service Guide ...
Page 1204: ...1192 Lenovo System x3650 M4 Installation and Service Guide ...
Page 1212: ...Taiwan BSMI RoHS declaration 1200 Lenovo System x3650 M4 Installation and Service Guide ...
Page 1221: ......
Page 1222: ......