PS220 Configuration & Operation Guide
237 PS220
Function & F
eatures
The table below lists all of the Parameters used in this function.
Parameter
Name
Value/Range
Notes
83.01
EXE P CLEAN SEQ
Defines how the cleaning sequence is executed.
NOT SEL (DEFAULT)
The pump cleaning sequence is disabled.
P CTRL DI3
The pump cleaning system is executed using DI3.
PS220
The pump cleaning system is executed by the
PS220 automatically.
83.02
REQ P CLEAN SEQ
Applicable only when 83.01 is set
to PS220.
Defines what triggers the request of the pump cleaning
sequence.
NOT SEL (DEFAULT)
Disable the Automatic execution of the PCS
TORQ
The request is triggered when 1.10 MOTOR TORQUE
exceeds the value set in 83.03 TORQ REQ for the
83.04 TON REQ.
Time of Day
This request is triggered when the time of day is
reached,
TORQ OR TIME of Day
This request is triggered by either motor torque or
run time.
83.03
TORQUE REQ
0.0-200.0%
120% [default]
Defines the motor torque threshold value in % above
nominal motor torque to trigger the execution of the
pump cleaning sequence.
83.04
TON REQ
0-100 Seconds
5s [default]
Time period before the pump cleaning sequence can
be triggered once the threshold torque is reached,
83.05
RUN TIME REQ
24-hour clock time in Hours,
Minutes, and seconds.
Defines the time of the day at which the pump
cleaning sequence executes automatically.
83.06
NUM OF CYCLES
1-10
2 [default]
Defines the number of cycles the pump cleaning
sequence can execute.
83.07
FWD RUN SPD
0.0-100.0%
100% [default]
Defines the forward running speed in % of
parameter 30.12, MAXIMUM SPEED.
83.08
FWD RUN TIME
0.0-100.0 Seconds 7s
[default]
Defines the forward running time of the pump
cleaning sequence.
83.09
FWD RUN ACC
0.0-100.0 Seconds 1s
[default]
Defines the forward acceleration rate during the
execution of the cleaning cycle.
83.10
FWD RUN DEC
0.0-100.0 Seconds 2s
[default]
Defines the forward deceleration rate during the
execution of the cleaning cycle.
83.11
ZERO SPEED PAUSE
0.0-100.0 Seconds 7s
[default]
Defines the pause time during the pump cleaning
sequence that the pump does not run when
switching from forward to reverse rotation.
Summary of Contents for PumpSmart PS220
Page 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Page 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Page 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 283: ...PS220 Configuration Operation Guide PS220 282 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 289: ...PS220 Configuration Operation Guide PS220 288 Ecodesign Regulation...
Page 292: ...PS220 Configuration Operation Guide 291 PS220 Fuses heat dissipation chart...