PS220 Configuration & Operation Guide
PS220 74
Pump & VFD
Protection
8. Configure the Delay time:
1. “ARROW RIGHT” To change
2. “ARROWS UP/DOWN” to change value
3. “Save”
4. “NEXT”
Note:
If the “Number of trials” and the “Delay time” exceeds the ”Total trials time” the PS220 will
not be able to reset automatically. The fault will need to be reset manually.
9. Exit Wizard
1. Select “No”