PS220 Configuration & Operation Guide
PS220 164
Functions &
Features
Notes:
1. De-Staging values for up to 6 pumps are set to default values in the PS220 Multipump Functionality.
For both Speed and Torque, these values are set to % of “Max Speed” (Parameter30.12). Recommendations for these
values are as follows:
2. If you are using Torque/Smart Control in lieu of Speed PS220 Miscellaneous Wizard choice 2, the recommended
values for Destaging are as follows:
3. If you are using Process Variable as your stage and destage value you should “draw out” and well define these
De-stage values for all pumps. The default values WILL NOT WORK PROPERRLY
Name
Value
Notes
Destage 2 75%
Adjust based on Static
Head
Destage 3 85%
Adjust 5% Higher than
Destage 2
Destage 4 92%
Adjust 3% Higher than
Destage 3
Destage 5 94%
Adjust 3% Higher than
Destage 4
Destage 6 96%
96% should not be
exceeded.
Name
Value
Notes
Destage 2 60%
Test all values. These are
system dependent
Destage 3 70%
Test all values. These are
system dependent
Destage 4 80%
Test all values. These are
system dependent
Destage 5 86%
Test all values. These are
system dependent
Destage 6 90%
Test all values. These are
system dependent
Summary of Contents for PumpSmart PS220
Page 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Page 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Page 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 283: ...PS220 Configuration Operation Guide PS220 282 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 289: ...PS220 Configuration Operation Guide PS220 288 Ecodesign Regulation...
Page 292: ...PS220 Configuration Operation Guide 291 PS220 Fuses heat dissipation chart...