PS220 Configuration & Operation Guide
PS220 80
Multipump
PS220 Configuration & Operation Guide
5. Configure the Stage and Destage Method
The default value is SPEED or TORQUE
1. “ARROW RIGHT” To change
2. “ARROWS” to change value
3. “Save”
4. “ARROW DOWN”
6. Configure the STAGE PROOF TIME:
The default is 20 Seconds
1. “ARROW RIGHT” To change
2. “ARROWS” to change value
3. “Save”
4. “ARROW DOWN”
7. Configure the DESTAGE PROOF TIME
The default value is 20 seconds.
1. “ARROW RIGHT” To change
2. “ARROWS” to change value
3. “Save”
4. “ARROW DOWN”
8. Configure the MIN PUMPS ON
1. “ARROW RIGHT” To change
2. “ARROWS” to change value
3. “Save”
4. “ARROW DOWN”