PS220 Configuration & Operation Guide
PS220 26
SmartFlow
3. Configure the Fluids Specific Gravity’s Source
Please refer to Specific Gravity in this manual for more detailed explanation.
A. SG RATED (Fixed)
The default value for Specific Gravity [SG] is 1.0.
NOTES:
1. This value should only be changed now if you choose to bypass the “Smartflow Tune” function.
2. If the Specific Gravity varies by more than 5%, a correction method will be necessary.
1. “ARROW RIGHT” to change
2. “ARROWS UP/DOWN” to change value
3. “Save”
4. “Next”
B. Specific Gravity (Variable)
1. Fluid Temperature measured with Transmitter:
When changes to the SG are directly related to a change in the fluid’s temperature, the PumpSmart PS220 can
monitor these changes using a temperature transmitter. This transmitter will need to be connected and configured
to an available Analog Input. The corrected values then can be used with the internal Smartflow calculations.
NOTE: YOU WILL NEED TO CONFIGURE THE AVAILABLE ANALOG INPUT THAT WILL BE USED. THIS WIZARD DOES
NOT PROVIDE FOR THIS. COMPLETING THIS CAN BE ACCOMPLISHED BY GOING TO:
Menu>PS220 Configuration>I/O Configuration>Select the Analog Input #>
Summary of Contents for PumpSmart PS220
Page 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Page 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Page 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 283: ...PS220 Configuration Operation Guide PS220 282 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 289: ...PS220 Configuration Operation Guide PS220 288 Ecodesign Regulation...
Page 292: ...PS220 Configuration Operation Guide 291 PS220 Fuses heat dissipation chart...