PS220 Configuration & Operation Guide
109 PS220
I/O
Configuration
8.3 Relay Configuration Wizard
The PumpSmart PS220 has 3 Form C “Dry Contact” relays on board as standard. They are fully configurable for different
pumping system and electrical system operating conditions, to include warnings, and for fault conditions. Relays will
revert to their original states once any warnings, faults, or the operating conditions that triggered them are reset or
cleared. Each can be forced on, off, and inverted. By default, Relay 1 is configured for Ready, Relay 2 is configured for
Running, and Relay 3 is configured for Fault. Additional relays can be added with the use of optional plug-in extension
modules available from ITT.
Note:
To access this Wizard from the Home Screen, follow the path: Menu>PS220 Configuration>I/O Configuration>No> (OR
Yes, if you are configuring the FIO-11optional Extension Module for the first time)>Relays >Select
The steps that you will perform:
1. Configure the Assignment for the Relay by Number.
2. Exit the Wizard
The Screen Shots that follow will show you step by step as you progress, from start to finish as you progress, how to con-
figure this functionality.
1. “ARROW UP/DOWN” to change
2. “SAVE” to continue
3. Repeat steps 1-2 for additional relays
that need configuration.
2. Exit Wizard
1. “Next” to end.
NOTE:
For “Other” contact your ITT Monitoring & Control Application Engineer or Commissioning Engineer.
Summary of Contents for PumpSmart PS220
Page 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Page 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Page 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 283: ...PS220 Configuration Operation Guide PS220 282 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 289: ...PS220 Configuration Operation Guide PS220 288 Ecodesign Regulation...
Page 292: ...PS220 Configuration Operation Guide 291 PS220 Fuses heat dissipation chart...