2. The settings for Parameters 37.11 through 15 should not have to be changed for a 1780 RPM
motor. They will need to be change for motors of lower or higher full load synchronous speeds
(1180 RPM and 3550 RPM). The recommendations are as follows:
37.11 = 8.5% of Full Load speed
37.12 = 42% of Full Load speed
37.13 = 72% of Full Load speed
37.14 = 84% of Full Load speed
37.15 = 100% of Full load speed
3. Parameters not mentioned do not apply to this function
4. Configure the time period before the drive will react when an underload condition exits. The
Default is 20 Seconds. The Ranges is 0-10,000 seconds.
Parameter
Description
Default in
RPM of the
Motor
Recommendation
Notes
37.11
1st X Axis
Intersection
Point
150
S e e N o t e s
Should be
10% of Max
Motor Speed
37.12
2nd X Axis
Intersection
Point
750
S e e N o t e s
Should be
50% of Max
Motor Speed
37.13
3rd X Axis
Intersection
Point
1290
S e e N o t e s
Should be
72% of Max
Motor Speed
37.14
4th X Axis
Intersection
Point
1500
S e e N o t e s
Should be
83% of Max
Motor Speed
37.15
5th X Axis
Intersection
Point
1800
S e e N o t e s
Should be
100% of Max
Motor Speed
Summary of Contents for PumpSmart PS220
Page 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Page 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Page 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 283: ...PS220 Configuration Operation Guide PS220 282 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 289: ...PS220 Configuration Operation Guide PS220 288 Ecodesign Regulation...
Page 292: ...PS220 Configuration Operation Guide 291 PS220 Fuses heat dissipation chart...