PS220 Configuration & Operation Guide
PS220 126
Functions &
Features
Auto Restart
The PS220 can be configured to automatically restart on conditions such as Power Failure, VFD faults, and
Pump Protection faults. It can be set to reset a fault(s) up to a limited number of sequential attempts. If after
these attempts the Fault condition did not clear or could not be reset the drive will produce a “Hard” Fault and
will have to be manually reset. See the Section on Fault Tracing in this Manual for further information on how
to restart the drive after these events.
By enabling 74.02 AUTO RESTART, 31.14 AUTO RESET TRIALS or 79.05 PUMP FAULT RESET functions
the driven equipment will automatically restart from either a power failure or fault condition if a start
signal is present. All precautions should be taken to ensure the driven equipment can be automatically
restarted. Failure to follow these instructions may result in physical injury or equipment damage.
WARNING
Power Failure Auto-Restart
The PS220 can be configured to start automatically following a power failure by configuring the following parameters:
Parameter
Name
Value/Range
Note
74.02
AUTO RESTART
ON
OFF [default]
Must be set to ON.
21.18
AUTO RESART TIME
0 Seconds
5 Seconds( default)
Must be set to “0”
seconds
NOTE:
Auto-Restart will not function with the “Keypad”, or any “Fieldbus” combination is configured for parameter
74.01, or when in “Local” Control Mode.
Summary of Contents for PumpSmart PS220
Page 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Page 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Page 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 283: ...PS220 Configuration Operation Guide PS220 282 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 289: ...PS220 Configuration Operation Guide PS220 288 Ecodesign Regulation...
Page 292: ...PS220 Configuration Operation Guide 291 PS220 Fuses heat dissipation chart...