PS220 Configuration & Operation Guide
15 PS220
Basic Startup
1. Request to perform a Motor ID Run.
1. “Select”
3. Wait
2. Run the ID.
1. Push the “Green Start Button”
Note.
Although the motor may not appear to respond to the
start command. There may be an audible high-pitched sound
coming from the motor which is normal.
Note.
If the motor is repaired or replaced in the future, a
Motor Identification run must be performed again to maintain
the accuracy of the PumpSmart drive.
DIIL Permissive
The PS220 will not run the motor unless
the Permissive input [DIIL] is closed
(24Vdc). This includes performing the
Motor ID Run. If not closed a warning
message will appear on the keypad
display:
The PS220 drive will come from the
factory with a jumper between the DIIL
input and 24Vdc. See Appendix A-4,
Instrument Wiring, for details on wiring
this switch.
Safe Torque Off
The PS220 will not run the motor unless
the Safe Torque Off (STO) is closed. The
Safe Torque Off inputs are typically used
for the external E-Stop circuit. If the
E-Stop is active (STO open) the keypad
will display:
The PS220 drive will come from the
factory with jumpers installed between
the STO Output and Inputs 1 and 2. If
an E-Stop push button is installed in
the STO circuit be sure the E-Stop is not
activated.
Summary of Contents for PumpSmart PS220
Page 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Page 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Page 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 283: ...PS220 Configuration Operation Guide PS220 282 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 289: ...PS220 Configuration Operation Guide PS220 288 Ecodesign Regulation...
Page 292: ...PS220 Configuration Operation Guide 291 PS220 Fuses heat dissipation chart...