PS220 Configuration & Operation Guide
PS220 76
Pump & VFD
Protection
2. Configure the Speed Override Pump Protection setting.
The PumpSmart PS220 can be configured to allow all of the Pump Protection configured to be active
when the Speed Override function is also active. The Default value is “Disabled”
1. “ARROW RIGHT” To change
2. “ARROW UP/DOWN” to change
3. “Save“
4. “ARROW DOWN”
3. Configure the Pump Fault Reset:
The PumpSmart PS220 can be configured to “Auto-Reset” up to a set number of times when the “Alarm
& Control” choice has been configured for the “Protection Response“. The Default value is 0, which
deactivates the function. The range is (0-19).
Notes:
1. This function is not available for the Secondary Protection A or B functionality.
2. The PS220 will automatically end the retry attempts and end any further attempts when the system
runs for more than 5 minutes, continuously, without the event(s) re-occurring.
1. “ARROW RIGHT” To change
2. “ARROWS” to change
3. “Save”
4. “ARROW DOWN”
4. Configure the Pump Fault Reset Delay
The Pump Fault Reset Delay can be configured to delay the time that The PS220 will wait until Auto-Re-
starting after a Pump Protection “Alarm and Control” action has been taken. The default is 60 seconds.
The range is 0 - 3600 seconds.
1. “ARROW RIGHT” To change
2. “ARROWS” to change
3. “Save”
4. “ARROW DOWN”
Summary of Contents for PumpSmart PS220
Page 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Page 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Page 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 283: ...PS220 Configuration Operation Guide PS220 282 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 289: ...PS220 Configuration Operation Guide PS220 288 Ecodesign Regulation...
Page 292: ...PS220 Configuration Operation Guide 291 PS220 Fuses heat dissipation chart...