PS220 Configuration & Operation Guide
PS220 90
W
ater
Functions
4. Configure the proof time before executing the PCS once the request torque
threshold is met.
1. “ARROW RIGHT” To change
2. “ARROWS” to change value
3. “Save”
4. “ARROW DOWN”
5. Configure the time of the day to execute the PCS.
1. “ARROW RIGHT” To change
2. “ARROWS” to change value
3. “Save”
4. “ARROW DOWN”
6. Configure the maximum number of cycles the PCS can execute.
1. “ARROW RIGHT” To change
2. “ARROWSUP/DOWN” to change value
3. “Save”
4. “ARROW DOWN”
7. Configure the forward running speed during the PCS.
1. “ARROW RIGHT” To change
2. “ARROWS” to change value
3. “Save”
4. “ARROW DOWN”
Summary of Contents for PumpSmart PS220
Page 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Page 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Page 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 283: ...PS220 Configuration Operation Guide PS220 282 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 289: ...PS220 Configuration Operation Guide PS220 288 Ecodesign Regulation...
Page 292: ...PS220 Configuration Operation Guide 291 PS220 Fuses heat dissipation chart...