PS220 Configuration & Operation Guide
155 PS220
Function & F
eatures
Motor Setup/Configuration
The PumpSmart PS220’s default mode of operation utilizes the Electric Motor connected and will run the Pump using
the Basic Speed Control Functionality. The Basic Startup will configure the PumpSmart PS220 with the language you
select, allow you to define the motor characteristics, execute a Motor ID, and verify correct motor rotation. You will then
select the start/stop method, the operating speed range, and the method used to send the speed set point reference for
the system to work.
This procedure provides a baseline for all the PumpSmart functionality to properly perform. The PumpSmart PS220 will
not operate unless the Electric Motor connected is configured with all necessary information required. It must be per-
formed prior to any other functions and or features can be configured.
This functionality can only be configured with the PumpSmart PS220 Configuration Wizard.
To access this Wizard, from the Home Screen follow the path: Menu>PS220 Configuration>Basic Startup>Edit Motor
Parameters>
The steps that you will perform are as follows:
1. Configure the Motor Information
2. Perform the Motor ID Run
3. Perform a Motor Jog for Direction
1. Configure the Motor Information
All this information can usually be found on the Motor Nameplate that should be physically attached to the Motor. If
the Nameplate is not available, you cannot proceed to any of the next steps.
1. Configure the Supply voltage On a new PS220 the supply
voltage will show “Not Given”. Select from the ranges shown.
2. Configure the Motor Full Load Amps or Current (FLA)
3. Configure the Motor Voltage
4. Configure the Motor frequency This will either be 50 or 60Hz.
5. Configure the Motor full load RPM. This number will not be
3600, 1800, (at 60 Hz), it will need to be the “Slip Speed” or
“Synchronous speed” of the motor.
6. Configure the Motor nominal power
Summary of Contents for PumpSmart PS220
Page 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Page 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Page 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 283: ...PS220 Configuration Operation Guide PS220 282 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 289: ...PS220 Configuration Operation Guide PS220 288 Ecodesign Regulation...
Page 292: ...PS220 Configuration Operation Guide 291 PS220 Fuses heat dissipation chart...