PS220 Configuration & Operation Guide
63 PS220
Pump & VFD Protection
3. Configure the Digital Input to be used.
1. “Arrow Up/Down” to Define
2. “Select”
3. “Select”
Notes:
1. It is recommended to use DI4 for Secondary Protection A and DI5 for Secondary Protection B
2. An unused Digital Input (DI) will need to be configured for either of these 2 choices to function. Please check
the settings of the Digital Inputs currently in use by going to: Menu>Parameters> Complete List>Scroll down to
Group 76>Select and View 76.09 through 76.14. If available for configuration, “NOT SELECTED” will be shown.
An Extension Card will need to be added and configured if they are all in use.
To Configure Secondary Protection B, follow the same steps as noted above.
4. Exit the Wizard “N0” Or “Yes” to Continue to 4.5 “Protection Options”
on page 110.