PS220 Configuration & Operation Guide
69 PS220
Pump & VFD Protection
7. Configure the Hysteresis Value.
The Default is .20 of the units chosen for the condition. The range is 0-9999.
1. “Arrow Right”
2. “Arrows to Define”
3. “Save”
4. “Next”
To Configure a Second Condition:
Notes:
For the configuration of the Second Condition only these steps would need to be followed.
1. Configure the Condition 2 Source.
2. Configure the Condition 2 Warning Limits High and/or Low Values.
3. Configure the Condition 2 Warning Alarm High and/or Low Values.
4. Configure the Condition 2 Response.
5. Configure the Condition 2 Hysteresis Value
8. Exit the Wizard
1. “Arrow Right” to change
2. “Arrows UP/DOWN” to Define
3. “Save”
4. “Arrow Down”
Continue to 4.5 “Protection Options Wizard” on page 110.
“No”
“No”