PS220 Configuration & Operation Guide
43 PS220
Process Control
3. Configure the Transmitter Location
The configuration of transmitter location on the PumpSmart SP220 identifies whether the transmitter is
on the suction side of the piping system or on the discharge.
1. “ARROW UP/DOWN” to change
2. “Select”
Note:
When choosing suction side, the software will automatically invert the actual signal. (A rising value will increase the
speed of the pump to maintain the process setpoint). Check to be sure that the transmitter being used does not do
this as standard.
Refer to the “Regulation Mode” in this manual for more information.
4. Configure the Transmitter Information Detail:
4.1. Configure the physical ID of the AI used. The location that the transmitter has been wired to.
See notes below
1. “ARROW UP/DOWN” to change
2. “Select”
Notes:
1. Refer to the Analog Input section in the Index for more information on these configuration steps.
2. When Selecting the Analog Input make sure that it is connected to the correct input. Refer to the wiring diagrams
in this manual.
3. The Analog Input physically used is either AI1 or AI2 unless an extension card has been installed.
Summary of Contents for PumpSmart PS220
Page 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Page 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Page 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 283: ...PS220 Configuration Operation Guide PS220 282 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 289: ...PS220 Configuration Operation Guide PS220 288 Ecodesign Regulation...
Page 292: ...PS220 Configuration Operation Guide 291 PS220 Fuses heat dissipation chart...