PS220 Configuration & Operation Guide
103 PS220
I/O
Configuration
4. Configure the value in mA for the Min value. The default is 4mA
1. “ARROW RIGHT” To change
1. “ARROWS” to change
2. “SAVE”
3. “ARROW DOWN”
5. Configure the value in mA for the Max value. The default is 20mA.
1. “ARROW RIGHT” To change
1. “ARROWS” to change
2. “SAVE”
3. “ARROW DOWN”
6. Configure the Scaled Min value for the AI.
This refers to the value that corresponds to the minimum of the signal for the 4mA scaled value. This is defaulted to 0.
1. “ARROWS” to change
2. “SAVE”
3. “ARROW DOWN”
1. “ARROW RIGHT” To change