PS220 Configuration & Operation Guide
PS220 12
Basic
Startup
2. Perform a Motor ID RUN
The PumpSmart PS220 drive uses specific motor details to create a mathematical model. This model en-
ables more accurate motor control and is created using the motor data you have just entered. The PS220
will be magnetizing the motor from 20 to 60 seconds at zero speed. This is called a Standstill ID run as
the motor will not turn. It is also called a MAG ID, or ID Run. Once all the motor data has been entered,
you will be prompted as follows:
Note – Although the motor may not appear to respond to the start command. There may be
an audible high-pitched sound coming from the motor which is normal.
Note – If the motor is repaired or replaced in the future, a Motor Identification run must be
performed again to maintain the accuracy of the PumpSmart drive.
The following procedure, while not spinning the motor, will energize
the motor. All safety precautions must be followed before initiating the
Motor ID run. Failure to do so could result in serious injury or death.
WARNING
1. Request to perform a Motor ID Run.
1. “Select”
2. Run the ID.
3. Wait
1. Push the “Green Start Button”
Summary of Contents for PumpSmart PS220
Page 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Page 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Page 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 283: ...PS220 Configuration Operation Guide PS220 282 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 289: ...PS220 Configuration Operation Guide PS220 288 Ecodesign Regulation...
Page 292: ...PS220 Configuration Operation Guide 291 PS220 Fuses heat dissipation chart...