PS220 Configuration & Operation Guide
PS220 130
Functions &
Features
6. Configure the Min Speed Stop Delay time.
The Default is 60 Seconds. The range is 0- 3600 seconds.
7. Configure the Hysteresis Value
Hysteresis is the monitored difference (window) between the warning and alarm values, and the actual values used to
deactivate a Condition event. It prevents a condition from continuously activating and deactivating when the monitored
value fluctuates above and below the High or Low limits.
The default is .20 of the units selected for the source. The range is .20 to 9999.00.
You may have to change the configuration of Parameter 80.19 to allow Monitoring of the values when the PumpSmart
PS220 is either Running or Always. The default is ALWAYS.
This change will need to be done manually by accessing that specific parameter directly:
From the HOME SCREEN follow the path: Menu>Parameters>Complete List>Arrow Down to GROUP 80>80.19>
Edit>Save
The Parameters used in configuring the condition monitoring function are listed in the table below.