PS220 Configuration & Operation Guide
249 PS220
Fault T
racing
To access the Event Log from the Home View follow the Path:
Menu>Event log>Select
The last 32 fault and warnings are stored in the drives event logs. They are date and time stamped so they can be used
for analysis. Details of each event can be reviewed by pressing the key below the word “Details”
There are multiple ways to reset or clear an active fault:
1. If the fault is still active it can be reset by hitting the key below the word “reset.”
2. A wired digital input can be cycled (low to high). Any available Digital input can be set up using the I/O Configuration
wizard.
3. Fieldbus control can be used. The proper configuration settings will have to be setup and communicated to the drive.
If using Fieldbus Start/stop a fault cannot be reset via the keypad or with a digital input. It must be reset with a Fiel
bus command. Please refer to the Fieldbus Quick start guide for more information.
4. The event log can be used to view fault(s) that need to be reset and reset them there.
5. Using an approved PC based tool (ABB Drive Composer) connected to the drives input.
6. A Bluetooth device that can run the ABB DRIVETUNE App
5. All Power can be cycled off to the drive, then wait until the keypad goes dark, and then apply all power on again.
Summary of Contents for PumpSmart PS220
Page 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Page 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Page 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 283: ...PS220 Configuration Operation Guide PS220 282 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 289: ...PS220 Configuration Operation Guide PS220 288 Ecodesign Regulation...
Page 292: ...PS220 Configuration Operation Guide 291 PS220 Fuses heat dissipation chart...