PS220 Configuration & Operation Guide
PS220 104
I/O
Configuration
7. Configure the Scaled Max value for the AI.
This refers to the value that corresponds to the maximum of the signal for the 20mA scaled value. This is defaulted to 100.
1. “ARROWS” to change
2. “SAVE”
3. “ARROW DOWN”
1. “ARROW RIGHT” To change
NOTE:
1. The configuration of AI2 would start as shown below:
Follow the steps 1-7 above that were used for AI1.
8. Exit Wizard
1. “Next” twice
2. “No”