PS220 Configuration & Operation Guide
PS220 68
Pump & VFD
Protection
4. Configure the Condition 1 Alarm Limits High (and/or Low) Value (If Necessary)
1. “Arrow Right” to change
2. “Arrow Up/Down” to define
3. “Save”
4. “Arrow Down”
Repeat steps 1- 4 again (If necessary)
5. Configure the Condition 1 Response Delay time.
The Default is 20 Seconds. The range is 0- 3600 seconds.
1. “Arrow Right” to change
2. “Arrows UP/DOWN” to Define
3. “Save”
4. “Arrow Down”
6. Configure the Min Speed Stop Delay time.
When the monitored condition triggers a Warning or Alarm, the PumpSmart PS220 can be configured to run at its
minimum speed for a timed duration. If the condition that triggered the warning has not cleared during this time, the
drive will fault off and stop. This is not a re-settable fault. The fault will have to be reset, and the drive issued a start
command again. Please refer to the section “Fault Tracing” in this manual. The Default is 0, which disables this
function. The range is (0- 3600 seconds)
1. “Arrow Right”
2. “Arrows to Define”
3. “Save”
4. “Arrow Down”