PS220 Configuration & Operation Guide
PS220 208
Functions &
Features
TO “TURN OFF” Smart Control, reverting to Speed PID Control, you will follow the identical steps noted above
and configure the settings as follows:
1. Configure the use of Speed for PID Process Control
Configure both “EXT2 control mode” AND “EXT1 CONTROL MODE” to SPEED.
2. Configure the Speed Ramp up and Ramp down times.
Configure both values to 0 Seconds.
3. Configure the Max Speed Value.
Configure the Max Speed value to the Motor Slip Speed used in Basic startup. You may view this in Parameter
99.09 to ensure that the correct value will be used.
4. Exit the Wizard
5. Access the PS220 MultiPump Control Wizard.
Re-Configure the Stage and De-stage values to the values as shown in the table below. Only configure the values
for the total number of pumps in use in the pumping system.
Parameter
Descrip
�
on
Recommended
Se
�
ng
Notes
81.09
Stage 2 Value
98%
Default se
�
ng
81.10
Stage 3 Value
98%
Default se
�
ng
81.11
Stage 4 Value
98%
Default se
�
ng
81.17
Stage 5 Value
98%
Default se
�
ng
81.18
Stage 6 Value
98%
Default se
�
ng
81.13
De-Stage 2 Value
75%
Validate during commissioning
81.14
De-Stage 3 Value
80%
Validate during commissioning
81.15
De-Stage 4 Value
85%
Validate during commissioning
81.21
De-Stage 5 Value
90%
Validate during commissioning
81.22
De-Stage 6 Value
92%
Validate during commissioning
Summary of Contents for PumpSmart PS220
Page 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Page 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Page 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 283: ...PS220 Configuration Operation Guide PS220 282 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 289: ...PS220 Configuration Operation Guide PS220 288 Ecodesign Regulation...
Page 292: ...PS220 Configuration Operation Guide 291 PS220 Fuses heat dissipation chart...