PS220 Configuration & Operation Guide
169 PS220
Function & F
eatures
10. Configure the Stage/De-Stage Values for Pumps 2, 3 etc.
The default values are as shown. Validate all during commissioning.
11. Exit the Wizard and repeat for the remaining Pumps.
12. Follow instruction below:
Once you have completed the Multipump Configuration Wizard you MUST send a setpoint reference
change from the source selected in Basic Startup, from and to each and every drive. This will ensure that
the reference changes on each drive’s keypad display. It confirms that the PS220’s are communicating with
each other. It should take 3-4 seconds for this change to visibly register across all of the individual drive’s
keypads.
Parameter
Descrip
�
on
Default Se
�
ng
81.09
Stage 2 Value
98%
81.10
Stage 3 Value
98%
81.11
Stage 4 Value
98%
81.17
Stage 5 Value
98%
81.18
Stage 6 Value
98%
81.13
De-Stage 2 Value
75%
81.14
De-Stage 3 Value
85%
81.15
De-Stage 4 Value
92%
81.21
De-Stage 5 Value
94%
81.22
De-Stage 6 Value
98%