PS220 Configuration & Operation Guide
57 PS220
Pump & VFD Protection
2. Configure the flow feedback source.
There are two choices for this configuration:
A. No (Default) this will utilize the values from Smartflow.
B. Yes. This choice requires an external flowmeter. If it has not already been con-
figured this Wizard will continue and guide you through the steps in adding it.
NOTE:
THIS CHOICE CANNOT BE USED FOR PUMP PROTECTION FOR INDIVIDUAL
PUMPS IN MUTIPUMP CONTROL.
For Choice 2A: “No”
For Choice 2B: “Yes”
“Select”
“Select”
For 2B: If “No”
NOTES:
1. If you are unsure how to configure the flow meter as shown with the screen shots above, please refer to the section on
Analog Inputs in this manual if necessary.
2. An unused AI will need to be used for this choice to function correctly. Please check the settings of the Analog Inputs in
use by going to: Menu>PARAMATERS> Complete List>Scroll down to Group 76>Select and View 76.01&02. If available,
they will show “NOT SELECTED”. You may have to add an Extension Card to use an additional input. (Not provided as
standard).