![background image](http://html.mh-extra.com/html/franklin-electric/cerus-x-drive-cxd-003a-4v/cerus-x-drive-cxd-003a-4v_installation-and-operation-manual_2328798085.webp)
OPERATION
Monitoring Functions
85
Monitoring Functions
Home Screen Status Displays
The Home Screen displays default and user-selectable information about the opera
-
tional status of the VFD. The keypad
ESC
key returns to the Home Screen from any
menu.
1.
Operating Status:
This field indicates the system actions currently active.
2.
Command Source:
This field identifies the currently configured source for RUN commands.
3.
Frequency Source:
This field identifies the currently configured source for speed (frequency) control.
4.
User Selectable Display Line 1:
Use Arrow and Enter keys to step through selections and to change
setpoints.
•
(H) Actual output speed when running (Hz) for both
HAND
and
AUTO
modes.
•
(F) Keypad Setpoint (Hz) for
HAND
mode. This is adjustable using the keypad. In
AUTO
mode, the
running frequency is displayed.
•
(P) PID Setpoint in application based units (PSI, inWC, etc.)
[SET–21]
. This is adjustable using the
keypad.
•
Use
Line Display 1 [SET-57]
to permanently set the viewable parameter, cycling the power of the drive
or keypad to update the display. User options include:
0_Freq Command
1_Output Frequency
2_Multi-Fn Display
3_Output Current
5.
User Selectable Display Line 2:
Displays Output Current.
6.
User Selectable Display Line 3:
Use Arrow keys to step through choices. This display corresponds to
choices in
[SET–57]
“Parameter Descriptions > SET Menu” on page 201
for a complete list of
options.
b
Run
H
A
58.7 PSI
60.00 Hz
K/K
2.22 Amp
JOG
View . Faults
1
2
3
4
5
6
BT
•
Run/Stop
•
Lubrication
•
Limit by PID 2
•
Limit by Level
•
Ctrl by PID 2
•
Limit by Temp
•
Stopped by AI
•
Stall
•
Backspin Timer
•
K = Keypad
•
R = RS485
•
T = Terminal control
•
O = Option board
•
K = Keypad/PID
•
R = RS485
•
V1 = from AV1
•
O = Option board
•
V2 = from AV2
•
1-15 = Step speed (DI)
•
C = from ACI
•
J = Jog frequency
Summary of Contents for CERUS X-DRIVE CXD-003A-4V
Page 2: ......
Page 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 2 Franklin Electric Co Inc ...
Page 96: ...OPERATION Protection Features 96 ...
Page 112: ...ADVANCED APPLICATION OPTIONS Multi Drive Configurations 112 ...
Page 124: ...COMMUNICATIONS BACnet Communication 124 ...
Page 128: ...ACCESSORIES Optional Extension Cards 128 Frame D Frame E Frame F ...
Page 129: ...ACCESSORIES Optional Extension Cards 129 Frame G Frame H ...
Page 132: ...ACCESSORIES Optional Extension Cards 132 ...
Page 234: ...PARAMETER REFERENCE TABLES Parameter Descriptions Motor Menu 234 ...
Page 250: ...GLOSSARY 250 ...