PARAMETER REFERENCE TABLES
Parameter Descriptions > ADVANCE 2 Menu
231
ADV2-50 2098 Y L-L Wake Time
0 to 6000 sec
(Low to Low Demand) is an adjustable setting for Low to Low Demand
wake up time, which should be determined during system startup. It is
recommended to set time in this parameter to 20-30% greater value than
[ADV2-47]
shows for proper Pipe Leak protection operation. Default = 14
sec.
ADV2-51 2099 Y L-H Wake Time
0 to 6000 sec
(Low to High Demand) is an adjustable setting for Low to High Demand
wake up time, which should be determined during system startup. It is
recommended to set time in this parameter to 10-20% greater value than
[ADV2-47]
shows to compensate for any future system changes. Default = 6
sec.
ADV2-52 2100 Y LD Set Point
0 to (variable)
Low Demand Set Point: Adjustable setting for Low Demand pressure set-
point from 0 to
PID F/B Max [SET-20]
x 0.95. It can be adjusted to lower or
higher than HD (Main) pressure set-point value to provide desired pres
-
sure and prevent overpressure trip at pump start in Low Demand situa
-
tion. Default = 70.0 PSI.
ADV2-53 2101 Y LD Max Freq
[SET-23]
to
[SET-22]
PID High Frequency Limit setting for Low Demand. Adjust to lower fre
-
quency setting to prevent overpressure trips during run but enough to
maintain pressure at LD Set-point. Default = 48.00 Hz.
ADV2-54 2102 Y LD Timer
0 to 600 sec
Adjustable setting for Low Demand mode time. When VFD determines
Low Demand mode during wake-up but at any point pressure cannot
reach
[ADV2-52]
set-point within
[ADV2-54]
timer, VFD will switch control to
High Demand mode. Default = 10 sec.
ADV2-55 2103 Y Clean Pump Sel
0_Disabled
1_Clean Pump
2_Anti-Jam
3_Clean/Anti-Jam
1_Clean Pump: Provide periodic
[ADV2-56]
fast ramping starts to clean
impeller.
2_Anti-Jam: If lock rotor condition is detected, VFD periodically (5 sec
-
onds) starts motor for 1 second in reverse direction to unjam impeller. VFD
performs this twice with 30 seconds wait time. If impeller is not freed, VFD
trips on overload.
ADV2-56 2104 Y Clean Pump Tmr 0.0 to 6000.0 min
Set periodic interval for initiating Clean Pump starts.
ADV2-58 2106 N Aux AI Select
0_AVI1
1_ACI
2_AVI2
Aux AI signal will be used for control features by analog level and 2nd PID
Loop. Select AI input to designate for Aux AI. The default is AVI1.
ADV2-59 2107 N Aux AI Unit
0_PSI
1_inWC
2_Feet
3_°F
4_CFM
5_GPM
6_%
7_Cust
8_inHg
9_m
10_mBar
11_Bar
12_kPa
13_°C
14_LPM
15_CMH
Select units of Aux AI.
ADV2-60 2108 N Aux Unit Format 0_1
1_0.1
2_0.01
Select precision of Aux AI.
ADV2-61 2109 N Aux Max Value
0 to 30000 (unit)
Set max value of Aux AI.
ADV2-62 2110 N Analog Trigger
0_Disable
1_Relay
2_Run Enable
3_Trip
0_ Feature disabled
1_VFD will activate selected relay in any VFD state at the
AI Trigger Level
[
ADV2-65]
and deactivate by hysteresis value depending on the
Trigger Type
[
ADV2-64]
.
2_Enables VFD run command when HOA is in Hand or Auto mode based
on Aux AI level depending on the
Trigger Type [ADV2-64]
.
3_ When it is set to Trip and signal reaches trigger level depending on
Trig
-
ger Type [ADV2-64]
selection, VFD will trip and will require reset. VFD can be
reset when AI signal changed by
Trigger Hysteresis [ADV2-66]
value.
CODE
Mod
Bu AR Display Name
Range
Description
Summary of Contents for CERUS X-DRIVE CXD-003A-4V
Page 2: ......
Page 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 2 Franklin Electric Co Inc ...
Page 96: ...OPERATION Protection Features 96 ...
Page 112: ...ADVANCED APPLICATION OPTIONS Multi Drive Configurations 112 ...
Page 124: ...COMMUNICATIONS BACnet Communication 124 ...
Page 128: ...ACCESSORIES Optional Extension Cards 128 Frame D Frame E Frame F ...
Page 129: ...ACCESSORIES Optional Extension Cards 129 Frame G Frame H ...
Page 132: ...ACCESSORIES Optional Extension Cards 132 ...
Page 234: ...PARAMETER REFERENCE TABLES Parameter Descriptions Motor Menu 234 ...
Page 250: ...GLOSSARY 250 ...