OPERATION
Control Options
66
•
AVI2 Analog
: Inputs from external controller, potentiometer, or other device.
•
COM Card:
Frequency input through communications protocol.
Hand Run Command [SET–10]:
Source of Run Command in Hand mode. VFD starts based on run command
from:
•
Keypad (Default):
Run command from Start/Stop buttons.
•
Digital Input:
Run command from digital input FWD or REV terminal.
•
RS485:
Run command from RS485 interface. Keypad STOP is disabled.
•
Com Card:
Run command from communications card.
•
Ext HOA in Hand:
Run command from digital input
[IO-21] ~ [IO-28]
set to
26_HOA Hand
.
Auto Speed Ref [SET–07]:
Source of Speed Reference in Auto mode. VFD runs at a frequency based on
input from:
•
Keypad:
VFD runs at a fixed frequency set on the Home Screen.
•
Up/Down DI:
Digital input increases or decreases speed when DI terminals
[IO-21] ~ [IO-28]
set to
16_Up
and
17_Down
.
•
AVI1 Analog:
Input from external controller, potentiometer, or other device.
•
ACI Analog:
Input from external controller, potentiometer, or other device.
•
AVI2 Analog:
Input from external controller, potentiometer, or other device.
•
RS485 Serial:
Frequency input through Modbus control.
•
COM Card:
Frequency input through communications protocol.
•
PID Output:
VFD speed reference will be provided by PID control based on the difference between
PID Setpoint [SET–21]
and transducer feedback values.
IMPORTANT:
When PID Mode is selected, additional parameter settings should be verified to ensure
“Standard Operation with PID Feedback Control” on page 69
for more infor
-
mation.
Auto Run Command [SET–08]:
Source of Run Command in Auto mode. VFD starts based on input from:
•
Keypad (Default):
Run command from
START
/
STOP
buttons.
•
Digital Input:
Run command from digital input FWD or REV terminal.
•
RS485:
Run command from RS485 interface. Keypad
STOP
is disabled.
•
Com Card:
Run command from communications card.
•
Ext HOA in Auto:
Run command from digital input
[IO-21] ~ [IO-28]
set to
27_HOA AUTO
.
Summary of Contents for CERUS X-DRIVE CXD-003A-4V
Page 2: ......
Page 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 2 Franklin Electric Co Inc ...
Page 96: ...OPERATION Protection Features 96 ...
Page 112: ...ADVANCED APPLICATION OPTIONS Multi Drive Configurations 112 ...
Page 124: ...COMMUNICATIONS BACnet Communication 124 ...
Page 128: ...ACCESSORIES Optional Extension Cards 128 Frame D Frame E Frame F ...
Page 129: ...ACCESSORIES Optional Extension Cards 129 Frame G Frame H ...
Page 132: ...ACCESSORIES Optional Extension Cards 132 ...
Page 234: ...PARAMETER REFERENCE TABLES Parameter Descriptions Motor Menu 234 ...
Page 250: ...GLOSSARY 250 ...