DRIVE CONFIGURATION
Default Settings Table - SET Menu
50
Default Settings Table - SET Menu
Parameters in highlighted rows are reset when the application is changed
[SET–00]
.
CODE
Display
Basic
Supply Fan Exhaust
Fan
Cooling
Tower
Centrifugal
Pump
Submersible
Pump
Vacuum
Pump
Constant
Torque
FE
MagForce PM Motor
SET-01 Input Phase
3-Phase
3-Phase
3-Phase
3-Phase
3-Phase
3-Phase
3-Phase
3-Phase
3-Phase
3-Phase
SET-02 Motor HP
By VFD
Rating
By VFD
Rating
By VFD
Rating
By VFD
Rating
By VFD
Rating
By VFD
Rating
By VFD
Rating
By VFD
Rating
By VFD
Rating
By VFD
Rating
SET-03 Motor FLA (SFA)
By VFD
Rating
By VFD
Rating
By VFD
Rating
By VFD
Rating
By VFD
Rating
By VFD
Rating
By VFD
Rating
By VFD
Rating
By VFD
Rating
By VFD
Rating
SET-04 Motor RPM
1750
1750
1750
1750
1750
3450
1750
1750
3600
3450
SET-05 Motor Voltage
By VFD
Rating
By VFD
Rating
By VFD
Rating
By VFD
Rating
By VFD
Rating
By VFD
Rating
By VFD
Rating
By VFD
Rating
By VFD
Rating
By VFD
Rating
SET-06 Motor Freq Sel
*
60 Hz
60 Hz
60 Hz
60 Hz
60 Hz
60 Hz
60 Hz
60 Hz
60 Hz
60 Hz
SET-07 Auto Speed Ref
ACI Analog PID Output PID Output PID Output PID Output PID Output PID Output ACI Analog PID Output ACI Analog
SET-08 Auto Run Cmd
Digital
Input
Keypad
Keypad
Keypad
Keypad
Keypad
Keypad
Keypad
Keypad
Keypad
SET-09 Hand Speed Ref
Keypad
Keypad
Keypad
Keypad
Keypad
Keypad
Keypad
Keypad
Keypad
Keypad
SET-10 Hand Run Cmd
Keypad
Keypad
Keypad
Keypad
Keypad
Keypad
Keypad
Keypad
Keypad
Keypad
SET-11
Accel Time
20 Sec
20 Sec
20 Sec
20 Sec
20 Sec
2 Sec
20 Sec
20 Sec
2 Sec
20 Sec
SET-12
Decel Time
30 Sec
30 Sec
30 Sec
30 Sec
30 Sec
2 Sec
30 Sec
30 Sec
2 Sec
30 Sec
SET-13
Low Freq Limit
20 Hz
20 Hz
20 Hz
20 Hz
20 Hz
30 Hz
20 Hz
0 Hz
60 Hz
40 Hz
SET-14
High Freq Limit
60 Hz
60 Hz
60 Hz
60 Hz
60 Hz
60 Hz
60 Hz
60 Hz
120 Hz
120 Hz
SET-15
Load Rotation
FWD Only FWD Only FWD Only FWD Only FWD Only
FWD Only
FWD Only FWD Only FWD & REV FWD Only
SET-16
Stop Mode
Coast
Coast
Coast
Coast
Decel
Coast
Coast
Decel
Coast
Coast
SET-17
PID Mode
Disable
PID Direct PID Inverse PID Inverse PID Direct
PID Direct
PID Direct PID Direct PID Direct PID Direct
SET-18
PID F/B Source
ACI
ACI
ACI
ACI
ACI
ACI
ACI
ACI
ACI
ACI
SET-19
PID F/B Unit
inWC
inWC
inWC
°F
PSI
PSI
inWC
PSI
PSI
inWC
SET-20 PID F/B Max
1 inWC
1 inWC
1 inWC
150 °F
100 PSI
100 PSI
406.9 inWC
100 PSI
100 PSI
1 inWC
SET-21
PID Set-point
0.5 inWC
0.5 inWC
0.5 inWC
76 °F
60 PSI
60 PSI
60 inWC
60 PSI
60 PSI
0.5 inWC
SET-22 PID Lo Hz Limit
20 Hz
20 Hz
20 Hz
20 Hz
20 Hz
30 Hz
20 Hz
20 Hz
60 Hz
40 Hz
SET-23 PID Hi Hz Limit
60 Hz
60 Hz
60 Hz
60 Hz
60 Hz
60 Hz
60 Hz
60 Hz
120 Hz
120 Hz
SET-24 PID P-Gain
1%
1%
1%
1%
2%
2%
1%
1%
2%
1%
SET-25 PID I-Time
1 Sec
1 Sec
1 Sec
1 Sec
1 Sec
1 Sec
1 Sec
0.5 Sec
0.5 Sec
1 Sec
SET-26 Sleep Mode
Disabled
Disabled
Disabled
Disabled
Sleep Only
Sleep Only
Disabled
Disabled
Sleep Only
Disabled
SET-27 Sleep Chk Time
10 Sec
10 Sec
10 Sec
10 Sec
10 Sec
10 Sec
10 Sec
10 Sec
10 Sec
10 Sec
SET-28 Sleep Delay Time
6 Sec
6 Sec
6 Sec
6 Sec
6 Sec
6 Sec
6 Sec
6 Sec
6 Sec
6 Sec
SET-29 S-Boost Value
3%
3%
3%
3%
3%
3%
3%
3%
3%
3%
SET-30 Sleep Boost Timer
10 Sec
10 Sec
10 Sec
10 Sec
10 Sec
10 Sec
10 Sec
10 Sec
10 Sec
10 Sec
SET-31
Wake-Up Level
0.45 inWC
0.5 inWC
0.5 inWC
75 °F
55 PSI
55 PSI
55 inWC
55 PSI
55 PSI
0.5 inWC
SET-32 S-Bump Timer
5 Sec
5 Sec
5 Sec
5 Sec
5 Sec
5 Sec
5 Sec
5 Sec
5 Sec
5 Sec
SET-33 Pipe Fill Timer
0 Min
0 Min
0 Min
0 Min
0 Min
0 Min
0 Min
0 Min
3 Min
0 Min
SET-34 Pipe Fill Exit Level
0.4 inWC
0.4 inWC
0.4 inWC
74 °F
25 PSI
25 PSI
25 inWC
25 PSI
25 PSI
0.4 inWC
SET-35 Pipe Fill Freq
47 Hz
47 Hz
47 Hz
47 Hz
47 Hz
47 Hz
47 Hz
47 Hz
95 Hz
95 Hz
SET-36 Broken Pipe Lvl
0 inWC
0 inWC
0inWC
0 °F
15 PSI
15 PSI
0 inWC
0 PSI
15 PSI
0.4 inWC
SET-37 Broken Pipe Freq
59.5 Hz
59.5 Hz
59.5 Hz
59.5 Hz
59.5 Hz
59.5 Hz
59.5 Hz
59.5 Hz
114 Hz
114 Hz
SET-38 Broken Pipe Dly
180 Sec
180 Sec
180 Sec
180 Sec
180 Sec
180 Sec
180 Sec
180 Sec
180 Sec
180 Sec
SET-39 OverPress Set
Disabled
Disabled
Disabled
Disabled
OP Auto
Reset
OP Auto
Reset
Disabled
OP Auto
Reset
OP Auto
Reset
Disabled
SET-40 OverPress Lvl
1 inWC
1 inWC
1 inWC
80 °F
80 PSI
80 PSI
80 inWC
80 PSI
80 PSI
1 inWC
SET-41
ULD Select
By Current By Current By Current By Current By Current
By Current
By Current By Current By Torque By Torque
SET-42 ULD Level
45%
45%
45%
45%
45%
70%
45%
45%
60%
45%
SET-43 ULD Frequency
30 Hz
30 Hz
30 Hz
30 Hz
30 Hz
59 Hz
30 Hz
20 Hz
60 Hz
40 Hz
SET-44 ULD Delay
2 Sec
2 Sec
2 Sec
2 Sec
2 Sec
2 Sec
2 Sec
2 Sec
2 Sec
2 Sec
SET-45 ULD Recovery T
0 Min
0 Min
0 Min
0 Min
30 Min
30 Min
0 Min
0 Min
30 Min
0 Min
SET-46 ULD Recover Cnt
Read Only Read Only Read Only Read Only Read Only
Read Only
Read Only Read Only Read Only Read Only
Summary of Contents for CERUS X-DRIVE CXD-003A-4V
Page 2: ......
Page 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 2 Franklin Electric Co Inc ...
Page 96: ...OPERATION Protection Features 96 ...
Page 112: ...ADVANCED APPLICATION OPTIONS Multi Drive Configurations 112 ...
Page 124: ...COMMUNICATIONS BACnet Communication 124 ...
Page 128: ...ACCESSORIES Optional Extension Cards 128 Frame D Frame E Frame F ...
Page 129: ...ACCESSORIES Optional Extension Cards 129 Frame G Frame H ...
Page 132: ...ACCESSORIES Optional Extension Cards 132 ...
Page 234: ...PARAMETER REFERENCE TABLES Parameter Descriptions Motor Menu 234 ...
Page 250: ...GLOSSARY 250 ...