SPECIFICATIONS
460V Class 100~675HP (75~500kW)
238
460V Class 100~675HP (75~500kW)
(1)
UL Type 1 kit comes with UL Open Type VFD which are Frame D and larger.
(2)
The VFD cannot produce output voltage greater than input voltage.
(3)
Variable torque (VT) motor rating based on a 120% overload for 1 minute. Constant Torque (CT) motor rating based
on 120% overload for 1 minute and 160% overload for 3 seconds.
Model (CXD-xxx-4V)
UL Type 1
(1)
150A
180A
220A
260A
310A
370A
460A
530A
616A
683A
770A
Frame Size
D
E
F
G
H
Input Ratings
Voltage
380 (-15%) ~ 480 VAC (+10%)
Frequency
50/60 Hz (± 5%)
Current -
Variable Torque
150
180
220
260
310
370
460
530
616
683
770
Current -
Constant Torque
114
157
167
207
240
300
380
400
494
555
625
Output Ratings
Max Carrier Freq
2.0 -10.0
kHz
2.0 - 9.0kHz
Voltage
(2)
3-phase, 380 ~ 480 VAC
(3)
Frequency
0.01 ~ 599 Hz
Efficiency
98%
Power Factor
>0.98
Weight kg (lbs.)
38.5 ± 1.5 (84.9 ± 3.3)
64.8 ± 1.5 (142.9 ± 3.3)
86.5 ± 1.5 (190.7 ± 3.3)
134 ± 4 (295.4 ± 8.9)
228 (635)
DC Choke
Built-in 3%
VFD Ratings with 3-Phase Input Power
Variable
Torque
Motor
(3)
Ratings
Max Amps
150
180
220
260
310
370
460
530
616
683
770
Capacity [kVA]
120
143
175
207
247
295
367
422
491
544
613
Max HP @ 460 V
Surface Motor
100
150
150
200
250
300
350
450
500
550
600
Max HP @ 460 V
4” Submersible
–
–
–
–
–
–
–
–
–
–
–
Max HP @ 460 V
6” Submersible
–
–
–
–
–
–
–
–
–
–
–
Max HP @ 460 V
8” Submersible
100
100
150
175
200
–
–
–
–
–
–
Constant
Torque
Motor
(3)
Ratings
Max Amps
110
150
180
220
260
310
370
460
550
616
683
Capacity [kVA]
88
120
143
175
207
247
295
367
438
491
544
Max HP @ 460 V
75
100
150
150
200
250
300
350
450
500
550
VFD Ratings with 1-Phase Input Power
Variable
Torque
Motor
Ratings
Max Amps
49.5
59.4
72.6
85.8
102.3
122.1
151.8
174.9
203.3
225.4
254.1
Max HP @ 460 V
Surface Motor
30
40
50
60
75
75
100
125
150
150
200
Max HP @ 460 V
4” Submersible
–
–
–
–
–
–
–
–
–
–
–
Max HP @ 460 V
6” Submersible
30
40
40
50
60
–
–
–
–
–
–
Max HP @ 460 V
8” Submersible
–
–
40
50
60
75
100
125
125
150
175
Constant
Torque
Motor
Ratings
Max Amps
36.3
49.5
59.4
72.6
85.8
102.3
122.1
151.8
181.5
203.3
225.4
Max HP @ 460 V
30
40
50
60
60
75
100
125
150
150
200
Summary of Contents for CERUS X-DRIVE CXD-003A-4V
Page 2: ......
Page 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 2 Franklin Electric Co Inc ...
Page 96: ...OPERATION Protection Features 96 ...
Page 112: ...ADVANCED APPLICATION OPTIONS Multi Drive Configurations 112 ...
Page 124: ...COMMUNICATIONS BACnet Communication 124 ...
Page 128: ...ACCESSORIES Optional Extension Cards 128 Frame D Frame E Frame F ...
Page 129: ...ACCESSORIES Optional Extension Cards 129 Frame G Frame H ...
Page 132: ...ACCESSORIES Optional Extension Cards 132 ...
Page 234: ...PARAMETER REFERENCE TABLES Parameter Descriptions Motor Menu 234 ...
Page 250: ...GLOSSARY 250 ...