MAINTENANCE
Troubleshooting
163
TRAP
(93)
CPU Trap 0 error
CPU instruction error
Action and Reset
Action level
Hardware detection
Action time
Immediately
Reset method
Cycle the power
Recorded
Yes
Possible Causes
Corrective Action
• Hardware failure
• EMI Interference
• CPU in infinite loop
• Check wiring and grounding for possible interference
• If error cannot be reset, please call Technical Support
Fault Display
Description
ULD
(175)
Underload (M)
Dry well (belt loss). No load on motor.
Action and Reset
Action level
Current or Torque is below
ULD Level [SET-42]
and above
ULD Frequency [SET-43]
Action time
ULD Delay [SET-44]
Related parameters
Refer to
“Underload Protection (Dry Well or Belt Loss)” on page 93
Reset method
Manually or Automatically. Refer to
“Underload Protection (Dry Well or Belt Loss)” on page 93
Reset condition
Correct overloading condition
Recorded
Yes
Possible Causes
Corrective Action
• Over-pumped well
• Broken shaft or coupling
• Blocked screen, worn pump
• Air/gas locked pump
• X-Drive not set properly for pump end
• Underload Sensitivity setting
incorrect
• Frequency near maximum with load less than
ULD Level [SET-42]
.
• System is drawing down to pump inlet (out of water).
• High static, light loading pump - reset
ULD Level [SET-42]
if not out of water.
• Check pump rotation, reconnect if necessary for proper rotation.
• Air/gas locked pump - if possible, set deeper in well to reduce.
• Verify
Motor FLA [SET-03]
(SFA) setting is correct. For FE MagForce application, make sure
[SET-03]
matches pump load’s rated current.
Fault Display
Description
WDTT
(71)
Watchdog
Watchdog error
Action and Reset
Action level
Hardware detection
Related parameters
N/A
Reset method
Cycle the power
Reset condition
N/A
Recorded
Yes
Possible Causes
Corrective Action
• Hardware interference
• Verify the wiring of the control circuit and wiring/grounding of the main circuit to prevent interference.
• If the WDTT fault still exists, please call Technical Support.
Fault Display
Description
Summary of Contents for CERUS X-DRIVE CXD-003A-4V
Page 2: ......
Page 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 2 Franklin Electric Co Inc ...
Page 96: ...OPERATION Protection Features 96 ...
Page 112: ...ADVANCED APPLICATION OPTIONS Multi Drive Configurations 112 ...
Page 124: ...COMMUNICATIONS BACnet Communication 124 ...
Page 128: ...ACCESSORIES Optional Extension Cards 128 Frame D Frame E Frame F ...
Page 129: ...ACCESSORIES Optional Extension Cards 129 Frame G Frame H ...
Page 132: ...ACCESSORIES Optional Extension Cards 132 ...
Page 234: ...PARAMETER REFERENCE TABLES Parameter Descriptions Motor Menu 234 ...
Page 250: ...GLOSSARY 250 ...