MAINTENANCE
Troubleshooting
179
oH1
(9)
Over heat 1 Warn
The AC motor drive detects over-heating of IGBT
Action and Reset
Action condition
The AC motor drive detects over-heating of IGBT, and over the protection level of oH1 warning.
When
[PROT-18]
is higher than the IGBT over-heating level, the drive shows oH1 error without displaying oH1 warning.
Action time
When IGBT temperature is higher than
[PROT-18]
Related parameters
[PROT-18]
Reset method
Automatically
Reset condition
The drive resets when IGBT temperature is lower than oH1 warning level minus (–) 5°C
Recorded
N/A
Possible Causes
Corrective Action
• Ambient temperature or temperature
inside the cabinet is too high, or there is
obstruction in the ventilation hole of the
control cabinet.
• Check if there is any obstruction on the
heat sink or if the fan is running
• Insufficient ventilation space
• Check if the drive matches the
corresponded loading
• The drive has run 100% or more of the
rated output for a long time
• Check the ambient temperature. Regularly inspect the ventilation hole of the control cabinet.
Change the installed place if there are heating objects, such as braking resistors, in the surroundings.
Install/ add cooling fan or air conditioner to lower the temperature inside the cabinet.
• Remove the obstruction or replace the cooling fan.
• Increase ventilation space of the drive.
• Decrease loading. Decrease the carrier. Replace with a drive with larger capacity.
• Replace with a drive with larger capacity.
Warning Display
Description
oH2
(10)
Over heat 2 Warn
The drive has detected over heat of the board-level component
Action and Reset
Action condition
oH2 error level minus (–) 5°C
Action time
The oH2 warning occurs when the board-level component temperature is higher than oH2 warning level
Reset method
Automatically
Reset condition
The drive resets when IGBT temperature is lower than oH1 warning level minus (–) 5°C
Recorded
N/A
Possible Causes
Corrective Action
• Ambient temperature or temperature
inside the cabinet is too high, or there is
obstruction in the ventilation hole of the
control cabinet.
• Check if there is any obstruction on the
heat sink or if the fan is running
• Insufficient ventilation space
• Check if the drive matches the
corresponded loading
• Check the ambient temperature. Regularly inspect the ventilation hole of the control cabinet.
Change the installed place if there are heating objects, such as braking resistors, in the surroundings.
Install/ add cooling fan or air conditioner to lower the temperature inside the cabinet.
• Remove the obstruction or replace the cooling fan.
• Increase ventilation space of the drive.
• Decrease loading. Decrease the carrier. Replace with a drive with larger capacity.
Warning Display
Description
Summary of Contents for CERUS X-DRIVE CXD-003A-4V
Page 2: ......
Page 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 2 Franklin Electric Co Inc ...
Page 96: ...OPERATION Protection Features 96 ...
Page 112: ...ADVANCED APPLICATION OPTIONS Multi Drive Configurations 112 ...
Page 124: ...COMMUNICATIONS BACnet Communication 124 ...
Page 128: ...ACCESSORIES Optional Extension Cards 128 Frame D Frame E Frame F ...
Page 129: ...ACCESSORIES Optional Extension Cards 129 Frame G Frame H ...
Page 132: ...ACCESSORIES Optional Extension Cards 132 ...
Page 234: ...PARAMETER REFERENCE TABLES Parameter Descriptions Motor Menu 234 ...