MAINTENANCE
Troubleshooting
151
oH1
(16)
IGBT over heat
IGBT temperature exceeds the protection level
Action and Reset
Action level
When IGBT is higher than the
[PROT-18]
overheating protection level, oH1 error occurs instead of oH1 warning.
Action time
100 ms
Related parameters
OH Warning [PROT-18]
and
Fan Control [PROT-45]
Reset method
Manually or Automatically if in Auto mode and Auto Restart is enabled.
Reset condition
IGBT temperature is 10 °C below error level.
Recorded
Yes
Possible Causes
Corrective Action
• Ambient temperature too high
• VFD size does not match load
• Direct sunlight
• Obstruction of flow
• Ensure that the ambient temperature falls within the specified temperature range.
• Make sure heat sink is not obstructed. Check if the fan is operating
• Check if there is enough ventilation clearance for the drive.
• Reduce load.
• Replace drive with a larger capacity model.
• Remove from direct sunlight.
Fault Display
Description
oH2
(17)
Heat Sink oH
Capacitance temperature causes heatsink overheating.
Action and Reset
Action level
Temperature error level depends on VFD model
Action time
100 ms
Reset method
Manually or Automatically if in Auto mode and Auto Restart is enabled.
Reset condition
Capacitance temperature is 10 °C below error level.
Recorded
Yes
Possible Causes
Corrective Action
• Ambient temperature too high
• VFD size does not match load
• Unstable power
• Ensure that the ambient temperature falls within the specified temperature range.
• Make sure heat sink is not obstructed. Check if the fan is operating
• Check if there is enough ventilation clearance for the drive.
Fault Display
Description
Summary of Contents for CERUS X-DRIVE CXD-003A-4V
Page 2: ......
Page 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 2 Franklin Electric Co Inc ...
Page 96: ...OPERATION Protection Features 96 ...
Page 112: ...ADVANCED APPLICATION OPTIONS Multi Drive Configurations 112 ...
Page 124: ...COMMUNICATIONS BACnet Communication 124 ...
Page 128: ...ACCESSORIES Optional Extension Cards 128 Frame D Frame E Frame F ...
Page 129: ...ACCESSORIES Optional Extension Cards 129 Frame G Frame H ...
Page 132: ...ACCESSORIES Optional Extension Cards 132 ...
Page 234: ...PARAMETER REFERENCE TABLES Parameter Descriptions Motor Menu 234 ...
Page 250: ...GLOSSARY 250 ...