ELECTRICAL INSTALLATION
Power Wiring Connections
40
Frame
Maximum Terminal Wire Size
Torque
Frame A
8 AWG
17.4 in-lbs (1.96 Nm)
Frame B
4 AWG
30.4 in-lbs (3.43 Nm)
Frame C
1/0 AWG
69.4 in-lbs (7.84 Nm)
Frame D0
2/0 AWG
69.4 in-lbs (7.84 Nm)
Frame D
300 MCM or 4/0 AWG
156 in-lbs (18 Nm)
Frame E
4/0 AWG*2
174 in-lbs (20 Nm)
Frame F
300 MCM*2 or 4/0 AWG*2
156 in-lbs (18 Nm)
Frame G,
Terminals R, S, & T
250 MCM*4
156 in-lbs (18 Nm)
Frame G,
Terminals U, V, & T
500 MCM*2
354 in-lbs (40 Nm)
Frame H
350 MCM*4
156 in-lbs (18 Nm)
Summary of Contents for CERUS X-DRIVE CXD-003A-4V
Page 2: ......
Page 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 2 Franklin Electric Co Inc ...
Page 96: ...OPERATION Protection Features 96 ...
Page 112: ...ADVANCED APPLICATION OPTIONS Multi Drive Configurations 112 ...
Page 124: ...COMMUNICATIONS BACnet Communication 124 ...
Page 128: ...ACCESSORIES Optional Extension Cards 128 Frame D Frame E Frame F ...
Page 129: ...ACCESSORIES Optional Extension Cards 129 Frame G Frame H ...
Page 132: ...ACCESSORIES Optional Extension Cards 132 ...
Page 234: ...PARAMETER REFERENCE TABLES Parameter Descriptions Motor Menu 234 ...
Page 250: ...GLOSSARY 250 ...