MAINTENANCE
Troubleshooting
167
CFrn
(42)
CAN/S FRAM fail
CANopen memory error
Action and Reset
Action condition
When the user update firmware version of the control board, the FRAM internal data will not be changed, then CFrn
fault will occur.
Action time
Immediately act when the fault is detected
Reset method
Manually
Reset condition
[ADV-03]
= 7
Recorded
When
[SET-08]
does not equal 3, CFrn is a warning and isn’t recorded.
Possible Causes
Corrective Action
• CANopen internal memory error
• Disable CANopen
• Reset CANopen (
[SET-07]
= 7)
• Reset CANopen station address
Warning Display
Description
CGdn
(36)
Guarding T-out
CANopen guarding time-out 1
Action and Reset
Action condition
When CANopen Node Guarding detects that one of the followers does not response, the CGdn error displays. The
upper unit sets factor and time during configuration.
Action time
The time that upper unit sets during configuration
Reset method
Manually
Reset condition
The upper unit sends a reset package to clear this fault
Recorded
N/A
Possible Causes
Corrective Action
• The guarding time is too short, or less
detection times
• Malfunction caused by interference
• Increase the guarding time (Index 100C) and detection times.
• Verify the wiring and grounding of the communication circuit. It is recommended to separate the
communication circuit from the main circuit, or wire in 90 degree for effective anti-interference
performance. Make sure the communication circuit is wired in series. Use CANopen cable or add
terminating resistance.
Warning Display
Description
CHbn
(37)
Heartbeat T-out
CANopen heartbeat error
Action and Reset
Action condition
When CANopen Heartbeat detects that one of the followers does not response, the CHbn error shows. The upper unit
sets the confirming time of producer and consumer during configuration.
Action time
The upper unit sets the confirming time of producer and consumer during configuration.
Reset method
Manually
Reset condition
The upper unit sends a reset package to clear this fault
Recorded
No
Possible Causes
Corrective Action
• The heartbeat time is too short
• Malfunction caused by interference
• Communication cable is broken or bad
connection
• Increase heartbeat time (Index 1016)
• Verify the wiring and grounding of the communication circuit. It is recommended to separate the
communication circuit from the main circuit, or wire in 90 degree for effective anti-interference
performance. Make sure the communication circuit is wired in series. Use CANopen cable or add
terminating resistance.
• Check or replace the communication cable.
Warning Display
Description
Summary of Contents for CERUS X-DRIVE CXD-003A-4V
Page 2: ......
Page 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 2 Franklin Electric Co Inc ...
Page 96: ...OPERATION Protection Features 96 ...
Page 112: ...ADVANCED APPLICATION OPTIONS Multi Drive Configurations 112 ...
Page 124: ...COMMUNICATIONS BACnet Communication 124 ...
Page 128: ...ACCESSORIES Optional Extension Cards 128 Frame D Frame E Frame F ...
Page 129: ...ACCESSORIES Optional Extension Cards 129 Frame G Frame H ...
Page 132: ...ACCESSORIES Optional Extension Cards 132 ...
Page 234: ...PARAMETER REFERENCE TABLES Parameter Descriptions Motor Menu 234 ...
Page 250: ...GLOSSARY 250 ...